Kabeltværsnit for 325 Ampere ved 600 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 325 A over 600 m ved 400V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 9.04V (2.26%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 29.81V (7.45%)
Voltage at Load391.0 VLine Loss: 5085.9 W
Max Power & Breaker225.17 kW350A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 600m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 4818.57 V (1204.64%) | 0.0 V | 7948.38 V (1987.1%) | 2712450.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 2891.14 V (722.78%) | 0.0 V | 4769.03 V (1192.26%) | 1627470.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1806.96 V (451.74%) | 0.0 V | 2980.64 V (745.16%) | 1017168.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 1204.64 V (301.16%) | 0.0 V | 1987.1 V (496.77%) | 678112.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 722.78 V (180.7%) | 0.0 V | 1192.26 V (298.06%) | 406867.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 451.74 V (112.94%) | 0.0 V | 745.16 V (186.29%) | 254292.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 289.11 V (72.28%) | 110.9 V | 476.9 V (119.23%) | 162747.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 206.51 V (51.63%) | 193.5 V | 340.64 V (85.16%) | 116247.9 W | Drop High |
| 50 mm² | 151 A | 118 A | 144.56 V (36.14%) | 255.4 V | 238.45 V (59.61%) | 81373.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 103.25 V (25.81%) | 296.7 V | 170.32 V (42.58%) | 58123.9 W | Drop High |
| 95 mm² | 232 A | 181 A | 76.08 V (19.02%) | 323.9 V | 125.5 V (31.38%) | 42828.2 W | Drop High |
| 120 mm² | 269 A | 210 A | 60.23 V (15.06%) | 339.8 V | 99.35 V (24.84%) | 33905.6 W | Drop High |
| 150 mm² | 309 A | 241 A | 48.19 V (12.05%) | 351.8 V | 79.48 V (19.87%) | 27124.5 W | Drop High |
| 185 mm² | 353 A | 275 A | 39.07 V (9.77%) | 360.9 V | 64.45 V (16.11%) | 21992.8 W | Drop High |
| 240 mm² | 415 A | 324 A | 30.12 V (7.53%) | 369.9 V | 49.68 V (12.42%) | 16952.8 W | Drop High |
| 300 mm² | 477 A | 372 A | 24.09 V (6.02%) | 375.9 V | 39.74 V (9.94%) | 13562.2 W | Drop High |
| 400 mm² | 570 A | 445 A | 18.07 V (4.52%) | 381.9 V | 29.81 V (7.45%) | 10171.7 W | ~ ≤5% |
FAQ — Kabeltværsnit for 325 Ampere ved 600 Meter (400V)
Hvilket kabeltværsnit kræves til 325A ved 600 meter (400V)?
Til 325 Ampere over 600 meter ved 400V anbefales 2× 400 mm² kobberkabel (spændingsfald 9.04V / 2.26%).
Hvor mange kW svarer 325A ved 400V til?
Det svarer til 225.17 kW med en anbefalet sikring på 350A.
Related Lengths & Currents (400V)
325A · 5m (400V)325A · 10m (400V)325A · 15m (400V)325A · 20m (400V)325A · 25m (400V)325A · 30m (400V)325A · 35m (400V)325A · 40m (400V)325A · 45m (400V)325A · 50m (400V)325A · 60m (400V)325A · 70m (400V)10A · 600m (400V)16A · 600m (400V)20A · 600m (400V)25A · 600m (400V)32A · 600m (400V)40A · 600m (400V)50A · 600m (400V)63A · 600m (400V)80A · 600m (400V)100A · 600m (400V)125A · 600m (400V)160A · 600m (400V)200A · 600m (400V)