Kabeltværsnit for 16 Ampere ved 600 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 16 A over 600 m ved 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 10.17V (2.54%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 11.74V (2.93%)
Voltage at Load389.8 VLine Loss: 281.7 W
Max Power & Breaker11.09 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A237.22 V (59.31%)162.8 V391.3 V (97.83%)6574.1 WDrop High
2.5 mm²24 A18 A142.33 V (35.58%)257.7 V234.78 V (58.7%)3944.4 WDrop High
4 mm²32 A25 A88.96 V (22.24%)311.0 V146.74 V (36.68%)2465.3 WDrop High
6 mm²41 A32 A59.31 V (14.83%)340.7 V97.83 V (24.46%)1643.5 WDrop High
10 mm²57 A44 A35.58 V (8.9%)364.4 V58.7 V (14.67%)986.1 WDrop High
16 mm²76 A59 A22.24 V (5.56%)377.8 V36.68 V (9.17%)616.3 WDrop High
25 mm²101 A78 A14.23 V (3.56%)385.8 V23.48 V (5.87%)394.4 W~ ≤5%
35 mm²125 A97 A10.17 V (2.54%)389.8 V16.77 V (4.19%)281.7 W✓ OK (≤3%)
50 mm²151 A118 A7.12 V (1.78%)392.9 V11.74 V (2.93%)197.2 W✓ OK (≤3%)
70 mm²192 A150 A5.08 V (1.27%)394.9 V8.39 V (2.1%)140.9 W✓ OK (≤3%)
95 mm²232 A181 A3.75 V (0.94%)396.3 V6.18 V (1.54%)103.8 W✓ OK (≤3%)
120 mm²269 A210 A2.97 V (0.74%)397.0 V4.89 V (1.22%)82.2 W✓ OK (≤3%)
150 mm²309 A241 A2.37 V (0.59%)397.6 V3.91 V (0.98%)65.7 W✓ OK (≤3%)
185 mm²353 A275 A1.92 V (0.48%)398.1 V3.17 V (0.79%)53.3 W✓ OK (≤3%)
240 mm²415 A324 A1.48 V (0.37%)398.5 V2.45 V (0.61%)41.1 W✓ OK (≤3%)
300 mm²477 A372 A1.19 V (0.3%)398.8 V1.96 V (0.49%)32.9 W✓ OK (≤3%)
400 mm²570 A445 A0.89 V (0.22%)399.1 V1.47 V (0.37%)24.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 16 Ampere ved 600 Meter (400V)

Hvilket kabeltværsnit kræves til 16A ved 600 meter (400V)?

Til 16 Ampere over 600 meter ved 400V anbefales 35 mm² kobberkabel (spændingsfald 10.17V / 2.54%).

Hvor mange kW svarer 16A ved 400V til?

Det svarer til 11.09 kW med en anbefalet sikring på 16A.