Kabeltværsnit for 375 Ampere ved 150 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 375 A over 150 m ved 230V.
Copper Cable (≤3% Drop)400 mm²Drop: 6.02V (2.62%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.93V (4.32%)
Voltage at Load224.0 VLine Loss: 2257.0 W
Max Power & Breaker86.25 kW400A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 150m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1605.0 V (697.83%) | 0.0 V | 2647.5 V (1151.09%) | 601875.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 963.0 V (418.7%) | 0.0 V | 1588.5 V (690.65%) | 361125.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 601.88 V (261.68%) | 0.0 V | 992.81 V (431.66%) | 225703.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 401.25 V (174.46%) | 0.0 V | 661.88 V (287.77%) | 150468.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 240.75 V (104.67%) | 0.0 V | 397.12 V (172.66%) | 90281.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 150.47 V (65.42%) | 79.5 V | 248.2 V (107.91%) | 56425.8 W | Drop High |
| 25 mm² | 101 A | 78 A | 96.3 V (41.87%) | 133.7 V | 158.85 V (69.07%) | 36112.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 68.79 V (29.91%) | 161.2 V | 113.46 V (49.33%) | 25794.6 W | Drop High |
| 50 mm² | 151 A | 118 A | 48.15 V (20.93%) | 181.9 V | 79.42 V (34.53%) | 18056.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 34.39 V (14.95%) | 195.6 V | 56.73 V (24.67%) | 12897.3 W | Drop High |
| 95 mm² | 232 A | 181 A | 25.34 V (11.02%) | 204.7 V | 41.8 V (18.18%) | 9503.3 W | Drop High |
| 120 mm² | 269 A | 210 A | 20.06 V (8.72%) | 209.9 V | 33.09 V (14.39%) | 7523.4 W | Drop High |
| 150 mm² | 309 A | 241 A | 16.05 V (6.98%) | 213.9 V | 26.47 V (11.51%) | 6018.8 W | Drop High |
| 185 mm² | 353 A | 275 A | 13.01 V (5.66%) | 217.0 V | 21.47 V (9.33%) | 4880.1 W | Drop High |
| 240 mm² | 415 A | 324 A | 10.03 V (4.36%) | 220.0 V | 16.55 V (7.19%) | 3761.7 W | ~ ≤5% |
| 300 mm² | 477 A | 372 A | 8.03 V (3.49%) | 222.0 V | 13.24 V (5.76%) | 3009.4 W | ~ ≤5% |
| 400 mm² | 570 A | 445 A | 6.02 V (2.62%) | 224.0 V | 9.93 V (4.32%) | 2257.0 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 375 Ampere ved 150 Meter (230V)
Hvilket kabeltværsnit kræves til 375A ved 150 meter (230V)?
Til 375 Ampere over 150 meter ved 230V anbefales 400 mm² kobberkabel (spændingsfald 6.02V / 2.62%).
Hvor mange kW svarer 375A ved 230V til?
Det svarer til 86.25 kW med en anbefalet sikring på 400A.
Related Lengths & Currents (230V)
375A · 5m (230V)375A · 10m (230V)375A · 15m (230V)375A · 20m (230V)375A · 25m (230V)375A · 30m (230V)375A · 35m (230V)375A · 40m (230V)375A · 45m (230V)375A · 50m (230V)375A · 60m (230V)375A · 70m (230V)10A · 150m (230V)16A · 150m (230V)20A · 150m (230V)25A · 150m (230V)32A · 150m (230V)40A · 150m (230V)50A · 150m (230V)63A · 150m (230V)80A · 150m (230V)100A · 150m (230V)125A · 150m (230V)160A · 150m (230V)200A · 150m (230V)