Kabeltværsnit for 375 Ampere ved 45 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 375 A over 45 m ved 230V.

Copper Cable (≤3% Drop)240 mm²Drop: 3.01V (1.31%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.98V (1.29%)
Voltage at Load227.0 VLine Loss: 1128.5 W
Max Power & Breaker86.25 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A481.5 V (209.35%)0.0 V794.25 V (345.33%)180562.5 WDrop High
2.5 mm²24 A18 A288.9 V (125.61%)0.0 V476.55 V (207.2%)108337.5 WDrop High
4 mm²32 A25 A180.56 V (78.51%)49.4 V297.84 V (129.5%)67710.9 WDrop High
6 mm²41 A32 A120.38 V (52.34%)109.6 V198.56 V (86.33%)45140.6 WDrop High
10 mm²57 A44 A72.22 V (31.4%)157.8 V119.14 V (51.8%)27084.4 WDrop High
16 mm²76 A59 A45.14 V (19.63%)184.9 V74.46 V (32.37%)16927.7 WDrop High
25 mm²101 A78 A28.89 V (12.56%)201.1 V47.65 V (20.72%)10833.8 WDrop High
35 mm²125 A97 A20.64 V (8.97%)209.4 V34.04 V (14.8%)7738.4 WDrop High
50 mm²151 A118 A14.45 V (6.28%)215.6 V23.83 V (10.36%)5416.9 WDrop High
70 mm²192 A150 A10.32 V (4.49%)219.7 V17.02 V (7.4%)3869.2 WDrop High
95 mm²232 A181 A7.6 V (3.31%)222.4 V12.54 V (5.45%)2851.0 WDrop High
120 mm²269 A210 A6.02 V (2.62%)224.0 V9.93 V (4.32%)2257.0 WDrop High
150 mm²309 A241 A4.81 V (2.09%)225.2 V7.94 V (3.45%)1805.6 WDrop High
185 mm²353 A275 A3.9 V (1.7%)226.1 V6.44 V (2.8%)1464.0 WDrop High
240 mm²415 A324 A3.01 V (1.31%)227.0 V4.96 V (2.16%)1128.5 W✓ OK (≤3%)
300 mm²477 A372 A2.41 V (1.05%)227.6 V3.97 V (1.73%)902.8 W✓ OK (≤3%)
400 mm²570 A445 A1.81 V (0.79%)228.2 V2.98 V (1.29%)677.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 375 Ampere ved 45 Meter (230V)

Hvilket kabeltværsnit kræves til 375A ved 45 meter (230V)?

Til 375 Ampere over 45 meter ved 230V anbefales 240 mm² kobberkabel (spændingsfald 3.01V / 1.31%).

Hvor mange kW svarer 375A ved 230V til?

Det svarer til 86.25 kW med en anbefalet sikring på 400A.