Kabeltværsnit for 375 Ampere ved 250 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 375 A over 250 m ved 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.01V (2.18%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.55V (7.19%)
Voltage at Load225.0 VLine Loss: 1880.8 W
Max Power & Breaker86.25 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2675.0 V (1163.04%)0.0 V4412.5 V (1918.48%)1003125.0 WDrop High
2.5 mm²24 A18 A1605.0 V (697.83%)0.0 V2647.5 V (1151.09%)601875.0 WDrop High
4 mm²32 A25 A1003.12 V (436.14%)0.0 V1654.69 V (719.43%)376171.9 WDrop High
6 mm²41 A32 A668.75 V (290.76%)0.0 V1103.12 V (479.62%)250781.2 WDrop High
10 mm²57 A44 A401.25 V (174.46%)0.0 V661.88 V (287.77%)150468.7 WDrop High
16 mm²76 A59 A250.78 V (109.04%)0.0 V413.67 V (179.86%)94043.0 WDrop High
25 mm²101 A78 A160.5 V (69.78%)69.5 V264.75 V (115.11%)60187.5 WDrop High
35 mm²125 A97 A114.64 V (49.84%)115.4 V189.11 V (82.22%)42991.1 WDrop High
50 mm²151 A118 A80.25 V (34.89%)149.8 V132.38 V (57.55%)30093.8 WDrop High
70 mm²192 A150 A57.32 V (24.92%)172.7 V94.55 V (41.11%)21495.5 WDrop High
95 mm²232 A181 A42.24 V (18.36%)187.8 V69.67 V (30.29%)15838.8 WDrop High
120 mm²269 A210 A33.44 V (14.54%)196.6 V55.16 V (23.98%)12539.1 WDrop High
150 mm²309 A241 A26.75 V (11.63%)203.2 V44.12 V (19.18%)10031.2 WDrop High
185 mm²353 A275 A21.69 V (9.43%)208.3 V35.78 V (15.56%)8133.4 WDrop High
240 mm²415 A324 A16.72 V (7.27%)213.3 V27.58 V (11.99%)6269.5 WDrop High
300 mm²477 A372 A13.38 V (5.82%)216.6 V22.06 V (9.59%)5015.6 WDrop High
400 mm²570 A445 A10.03 V (4.36%)220.0 V16.55 V (7.19%)3761.7 W~ ≤5%

FAQ — Kabeltværsnit for 375 Ampere ved 250 Meter (230V)

Hvilket kabeltværsnit kræves til 375A ved 250 meter (230V)?

Til 375 Ampere over 250 meter ved 230V anbefales 2× 400 mm² kobberkabel (spændingsfald 5.01V / 2.18%).

Hvor mange kW svarer 375A ved 230V til?

Det svarer til 86.25 kW med en anbefalet sikring på 400A.