Kabeltværsnit for 375 Ampere ved 300 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 375 A over 300 m ved 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 10.42V (2.61%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 17.2V (4.3%)
Voltage at Load389.6 VLine Loss: 6771.1 W
Max Power & Breaker259.81 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2779.94 V (694.99%)0.0 V4585.6 V (1146.4%)1805625.0 WDrop High
2.5 mm²24 A18 A1667.96 V (416.99%)0.0 V2751.36 V (687.84%)1083375.0 WDrop High
4 mm²32 A25 A1042.48 V (260.62%)0.0 V1719.6 V (429.9%)677109.4 WDrop High
6 mm²41 A32 A694.99 V (173.75%)0.0 V1146.4 V (286.6%)451406.2 WDrop High
10 mm²57 A44 A416.99 V (104.25%)0.0 V687.84 V (171.96%)270843.8 WDrop High
16 mm²76 A59 A260.62 V (65.15%)139.4 V429.9 V (107.48%)169277.3 WDrop High
25 mm²101 A78 A166.8 V (41.7%)233.2 V275.14 V (68.78%)108337.5 WDrop High
35 mm²125 A97 A119.14 V (29.79%)280.9 V196.53 V (49.13%)77383.9 WDrop High
50 mm²151 A118 A83.4 V (20.85%)316.6 V137.57 V (34.39%)54168.7 WDrop High
70 mm²192 A150 A59.57 V (14.89%)340.4 V98.26 V (24.57%)38692.0 WDrop High
95 mm²232 A181 A43.89 V (10.97%)356.1 V72.4 V (18.1%)28509.9 WDrop High
120 mm²269 A210 A34.75 V (8.69%)365.3 V57.32 V (14.33%)22570.3 WDrop High
150 mm²309 A241 A27.8 V (6.95%)372.2 V45.86 V (11.46%)18056.2 WDrop High
185 mm²353 A275 A22.54 V (5.64%)377.5 V37.18 V (9.3%)14640.2 WDrop High
240 mm²415 A324 A17.37 V (4.34%)382.6 V28.66 V (7.17%)11285.2 W~ ≤5%
300 mm²477 A372 A13.9 V (3.47%)386.1 V22.93 V (5.73%)9028.1 W~ ≤5%
400 mm²570 A445 A10.42 V (2.61%)389.6 V17.2 V (4.3%)6771.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 375 Ampere ved 300 Meter (400V)

Hvilket kabeltværsnit kræves til 375A ved 300 meter (400V)?

Til 375 Ampere over 300 meter ved 400V anbefales 400 mm² kobberkabel (spændingsfald 10.42V / 2.61%).

Hvor mange kW svarer 375A ved 400V til?

Det svarer til 259.81 kW med en anbefalet sikring på 400A.