⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 375 Ampere ved 5 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 375 A over 5 m ved 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 0.29V (0.07%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.29V (0.07%)
Voltage at Load399.7 VLine Loss: 188.1 W
Max Power & Breaker259.81 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A46.33 V (11.58%)353.7 V76.43 V (19.11%)30093.8 WDrop High
2.5 mm²24 A18 A27.8 V (6.95%)372.2 V45.86 V (11.46%)18056.2 WDrop High
4 mm²32 A25 A17.37 V (4.34%)382.6 V28.66 V (7.17%)11285.2 WDrop High
6 mm²41 A32 A11.58 V (2.9%)388.4 V19.11 V (4.78%)7523.4 WDrop High
10 mm²57 A44 A6.95 V (1.74%)393.1 V11.46 V (2.87%)4514.1 WDrop High
16 mm²76 A59 A4.34 V (1.09%)395.7 V7.17 V (1.79%)2821.3 WDrop High
25 mm²101 A78 A2.78 V (0.69%)397.2 V4.59 V (1.15%)1805.6 WDrop High
35 mm²125 A97 A1.99 V (0.5%)398.0 V3.28 V (0.82%)1289.7 WDrop High
50 mm²151 A118 A1.39 V (0.35%)398.6 V2.29 V (0.57%)902.8 WDrop High
70 mm²192 A150 A0.99 V (0.25%)399.0 V1.64 V (0.41%)644.9 WDrop High
95 mm²232 A181 A0.73 V (0.18%)399.3 V1.21 V (0.3%)475.2 WDrop High
120 mm²269 A210 A0.58 V (0.14%)399.4 V0.96 V (0.24%)376.2 WDrop High
150 mm²309 A241 A0.46 V (0.12%)399.5 V0.76 V (0.19%)300.9 WDrop High
185 mm²353 A275 A0.38 V (0.09%)399.6 V0.62 V (0.15%)244.0 WDrop High
240 mm²415 A324 A0.29 V (0.07%)399.7 V0.48 V (0.12%)188.1 W✓ OK (≤3%)
300 mm²477 A372 A0.23 V (0.06%)399.8 V0.38 V (0.1%)150.5 W✓ OK (≤3%)
400 mm²570 A445 A0.17 V (0.04%)399.8 V0.29 V (0.07%)112.9 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 375 Ampere ved 5 Meter (400V)

Hvilket kabeltværsnit kræves til 375A ved 5 meter (400V)?

Til 375 Ampere over 5 meter ved 400V anbefales 240 mm² kobberkabel (spændingsfald 0.29V / 0.07%).

Hvor mange kW svarer 375A ved 400V til?

Det svarer til 259.81 kW med en anbefalet sikring på 400A.