Kabeltværsnit for 425 Ampere ved 80 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 425 A over 80 m ved 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 4.85V (2.11%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.0V (2.61%)
Voltage at Load225.1 VLine Loss: 2061.5 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A970.13 V (421.8%)0.0 V1600.27 V (695.77%)412306.7 WDrop High
2.5 mm²24 A18 A582.08 V (253.08%)0.0 V960.16 V (417.46%)247384.0 WDrop High
4 mm²32 A25 A363.8 V (158.17%)0.0 V600.1 V (260.91%)154615.0 WDrop High
6 mm²41 A32 A242.53 V (105.45%)0.0 V400.07 V (173.94%)103076.7 WDrop High
10 mm²57 A44 A145.52 V (63.27%)84.5 V240.04 V (104.37%)61846.0 WDrop High
16 mm²76 A59 A90.95 V (39.54%)139.1 V150.03 V (65.23%)38653.8 WDrop High
25 mm²101 A78 A58.21 V (25.31%)171.8 V96.02 V (41.75%)24738.4 WDrop High
35 mm²125 A97 A41.58 V (18.08%)188.4 V68.58 V (29.82%)17670.3 WDrop High
50 mm²151 A118 A29.1 V (12.65%)200.9 V48.01 V (20.87%)12369.2 WDrop High
70 mm²192 A150 A20.79 V (9.04%)209.2 V34.29 V (14.91%)8835.1 WDrop High
95 mm²232 A181 A15.32 V (6.66%)214.7 V25.27 V (10.99%)6510.1 WDrop High
120 mm²269 A210 A12.13 V (5.27%)217.9 V20.0 V (8.7%)5153.8 WDrop High
150 mm²309 A241 A9.7 V (4.22%)220.3 V16.0 V (6.96%)4123.1 WDrop High
185 mm²353 A275 A7.87 V (3.42%)222.1 V12.98 V (5.64%)3343.0 WDrop High
240 mm²415 A324 A6.06 V (2.64%)223.9 V10.0 V (4.35%)2576.9 WDrop High
300 mm²477 A372 A4.85 V (2.11%)225.1 V8.0 V (3.48%)2061.5 W✓ OK (≤3%)
400 mm²570 A445 A3.64 V (1.58%)226.4 V6.0 V (2.61%)1546.2 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 425 Ampere ved 80 Meter (230V)

Hvilket kabeltværsnit kræves til 425A ved 80 meter (230V)?

Til 425 Ampere over 80 meter ved 230V anbefales 300 mm² kobberkabel (spændingsfald 4.85V / 2.11%).

Hvor mange kW svarer 425A ved 230V til?

Det svarer til 97.75 kW med en anbefalet sikring på 450A.