Kabeltværsnit for 160 Ampere ved 80 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 160 A over 80 m ved 230V.
Copper Cable (≤3% Drop)95 mm²Drop: 5.77V (2.51%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 6.02V (2.62%)
Voltage at Load224.2 VLine Loss: 922.7 W
Max Power & Breaker36.8 kW160A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 80m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 365.23 V (158.79%) | 0.0 V | 602.45 V (261.94%) | 58436.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 219.14 V (95.28%) | 10.9 V | 361.47 V (157.16%) | 35061.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 136.96 V (59.55%) | 93.0 V | 225.92 V (98.23%) | 21913.6 W | Drop High |
| 6 mm² | 41 A | 32 A | 91.31 V (39.7%) | 138.7 V | 150.61 V (65.48%) | 14609.1 W | Drop High |
| 10 mm² | 57 A | 44 A | 54.78 V (23.82%) | 175.2 V | 90.37 V (39.29%) | 8765.4 W | Drop High |
| 16 mm² | 76 A | 59 A | 34.24 V (14.89%) | 195.8 V | 56.48 V (24.56%) | 5478.4 W | Drop High |
| 25 mm² | 101 A | 78 A | 21.91 V (9.53%) | 208.1 V | 36.15 V (15.72%) | 3506.2 W | Drop High |
| 35 mm² | 125 A | 97 A | 15.65 V (6.81%) | 214.3 V | 25.82 V (11.23%) | 2504.4 W | Drop High |
| 50 mm² | 151 A | 118 A | 10.96 V (4.76%) | 219.0 V | 18.07 V (7.86%) | 1753.1 W | Drop High |
| 70 mm² | 192 A | 150 A | 7.83 V (3.4%) | 222.2 V | 12.91 V (5.61%) | 1252.2 W | ~ ≤5% |
| 95 mm² | 232 A | 181 A | 5.77 V (2.51%) | 224.2 V | 9.51 V (4.14%) | 922.7 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 4.57 V (1.98%) | 225.4 V | 7.53 V (3.27%) | 730.5 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 3.65 V (1.59%) | 226.3 V | 6.02 V (2.62%) | 584.4 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 2.96 V (1.29%) | 227.0 V | 4.88 V (2.12%) | 473.8 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 2.28 V (0.99%) | 227.7 V | 3.77 V (1.64%) | 365.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 1.83 V (0.79%) | 228.2 V | 3.01 V (1.31%) | 292.2 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.37 V (0.6%) | 228.6 V | 2.26 V (0.98%) | 219.1 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 160 Ampere ved 80 Meter (230V)
Hvilket kabeltværsnit kræves til 160A ved 80 meter (230V)?
Til 160 Ampere over 80 meter ved 230V anbefales 95 mm² kobberkabel (spændingsfald 5.77V / 2.51%).
Hvor mange kW svarer 160A ved 230V til?
Det svarer til 36.8 kW med en anbefalet sikring på 160A.
Related Lengths & Currents (230V)
160A · 5m (230V)160A · 10m (230V)160A · 15m (230V)160A · 20m (230V)160A · 25m (230V)160A · 30m (230V)160A · 35m (230V)160A · 40m (230V)160A · 45m (230V)160A · 50m (230V)160A · 60m (230V)160A · 70m (230V)10A · 80m (230V)16A · 80m (230V)20A · 80m (230V)25A · 80m (230V)32A · 80m (230V)40A · 80m (230V)50A · 80m (230V)63A · 80m (230V)80A · 80m (230V)100A · 80m (230V)125A · 80m (230V)200A · 80m (230V)