Kabeltværsnit for 160 Ampere ved 80 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 160 A over 80 m ved 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 5.77V (2.51%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 6.02V (2.62%)
Voltage at Load224.2 VLine Loss: 922.7 W
Max Power & Breaker36.8 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A365.23 V (158.79%)0.0 V602.45 V (261.94%)58436.3 WDrop High
2.5 mm²24 A18 A219.14 V (95.28%)10.9 V361.47 V (157.16%)35061.8 WDrop High
4 mm²32 A25 A136.96 V (59.55%)93.0 V225.92 V (98.23%)21913.6 WDrop High
6 mm²41 A32 A91.31 V (39.7%)138.7 V150.61 V (65.48%)14609.1 WDrop High
10 mm²57 A44 A54.78 V (23.82%)175.2 V90.37 V (39.29%)8765.4 WDrop High
16 mm²76 A59 A34.24 V (14.89%)195.8 V56.48 V (24.56%)5478.4 WDrop High
25 mm²101 A78 A21.91 V (9.53%)208.1 V36.15 V (15.72%)3506.2 WDrop High
35 mm²125 A97 A15.65 V (6.81%)214.3 V25.82 V (11.23%)2504.4 WDrop High
50 mm²151 A118 A10.96 V (4.76%)219.0 V18.07 V (7.86%)1753.1 WDrop High
70 mm²192 A150 A7.83 V (3.4%)222.2 V12.91 V (5.61%)1252.2 W~ ≤5%
95 mm²232 A181 A5.77 V (2.51%)224.2 V9.51 V (4.14%)922.7 W✓ OK (≤3%)
120 mm²269 A210 A4.57 V (1.98%)225.4 V7.53 V (3.27%)730.5 W✓ OK (≤3%)
150 mm²309 A241 A3.65 V (1.59%)226.3 V6.02 V (2.62%)584.4 W✓ OK (≤3%)
185 mm²353 A275 A2.96 V (1.29%)227.0 V4.88 V (2.12%)473.8 W✓ OK (≤3%)
240 mm²415 A324 A2.28 V (0.99%)227.7 V3.77 V (1.64%)365.2 W✓ OK (≤3%)
300 mm²477 A372 A1.83 V (0.79%)228.2 V3.01 V (1.31%)292.2 W✓ OK (≤3%)
400 mm²570 A445 A1.37 V (0.6%)228.6 V2.26 V (0.98%)219.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 160 Ampere ved 80 Meter (230V)

Hvilket kabeltværsnit kræves til 160A ved 80 meter (230V)?

Til 160 Ampere over 80 meter ved 230V anbefales 95 mm² kobberkabel (spændingsfald 5.77V / 2.51%).

Hvor mange kW svarer 160A ved 230V til?

Det svarer til 36.8 kW med en anbefalet sikring på 160A.