Kabeltværsnit for 450 Ampere ved 150 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 450 A over 150 m ved 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.61V (1.57%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.91V (5.18%)
Voltage at Load226.4 VLine Loss: 1625.0 W
Max Power & Breaker103.5 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1926.0 V (837.39%)0.0 V3177.0 V (1381.3%)866700.0 WDrop High
2.5 mm²24 A18 A1155.6 V (502.43%)0.0 V1906.2 V (828.78%)520020.0 WDrop High
4 mm²32 A25 A722.25 V (314.02%)0.0 V1191.38 V (517.99%)325012.5 WDrop High
6 mm²41 A32 A481.5 V (209.35%)0.0 V794.25 V (345.33%)216675.0 WDrop High
10 mm²57 A44 A288.9 V (125.61%)0.0 V476.55 V (207.2%)130005.0 WDrop High
16 mm²76 A59 A180.56 V (78.51%)49.4 V297.84 V (129.5%)81253.1 WDrop High
25 mm²101 A78 A115.56 V (50.24%)114.4 V190.62 V (82.88%)52002.0 WDrop High
35 mm²125 A97 A82.54 V (35.89%)147.5 V136.16 V (59.2%)37144.3 WDrop High
50 mm²151 A118 A57.78 V (25.12%)172.2 V95.31 V (41.44%)26001.0 WDrop High
70 mm²192 A150 A41.27 V (17.94%)188.7 V68.08 V (29.6%)18572.1 WDrop High
95 mm²232 A181 A30.41 V (13.22%)199.6 V50.16 V (21.81%)13684.7 WDrop High
120 mm²269 A210 A24.07 V (10.47%)205.9 V39.71 V (17.27%)10833.8 WDrop High
150 mm²309 A241 A19.26 V (8.37%)210.7 V31.77 V (13.81%)8667.0 WDrop High
185 mm²353 A275 A15.62 V (6.79%)214.4 V25.76 V (11.2%)7027.3 WDrop High
240 mm²415 A324 A12.04 V (5.23%)218.0 V19.86 V (8.63%)5416.9 WDrop High
300 mm²477 A372 A9.63 V (4.19%)220.4 V15.88 V (6.91%)4333.5 W~ ≤5%
400 mm²570 A445 A7.22 V (3.14%)222.8 V11.91 V (5.18%)3250.1 W~ ≤5%

FAQ — Kabeltværsnit for 450 Ampere ved 150 Meter (230V)

Hvilket kabeltværsnit kræves til 450A ved 150 meter (230V)?

Til 450 Ampere over 150 meter ved 230V anbefales 2× 400 mm² kobberkabel (spændingsfald 3.61V / 1.57%).

Hvor mange kW svarer 450A ved 230V til?

Det svarer til 103.5 kW med en anbefalet sikring på 450A.