Kabeltværsnit for 5 Ampere ved 120 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 5 A over 120 m ved 400V.
Copper Cable (≤3% Drop)2.5 mm²Drop: 8.9V (2.22%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 9.17V (2.29%)
Voltage at Load391.1 VLine Loss: 77.0 W
Max Power & Breaker3.46 kW6A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 120m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 14.83 V (3.71%) | 385.2 V | 24.46 V (6.11%) | 128.4 W | ~ ≤5% |
| 2.5 mm² | 24 A | 18 A | 8.9 V (2.22%) | 391.1 V | 14.67 V (3.67%) | 77.0 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 5.56 V (1.39%) | 394.4 V | 9.17 V (2.29%) | 48.1 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 3.71 V (0.93%) | 396.3 V | 6.11 V (1.53%) | 32.1 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 2.22 V (0.56%) | 397.8 V | 3.67 V (0.92%) | 19.3 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.39 V (0.35%) | 398.6 V | 2.29 V (0.57%) | 12.0 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.89 V (0.22%) | 399.1 V | 1.47 V (0.37%) | 7.7 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.64 V (0.16%) | 399.4 V | 1.05 V (0.26%) | 5.5 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.44 V (0.11%) | 399.6 V | 0.73 V (0.18%) | 3.9 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.32 V (0.08%) | 399.7 V | 0.52 V (0.13%) | 2.8 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.23 V (0.06%) | 399.8 V | 0.39 V (0.1%) | 2.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.19 V (0.05%) | 399.8 V | 0.31 V (0.08%) | 1.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.15 V (0.04%) | 399.9 V | 0.24 V (0.06%) | 1.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.12 V (0.03%) | 399.9 V | 0.2 V (0.05%) | 1.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.09 V (0.02%) | 399.9 V | 0.15 V (0.04%) | 0.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.07 V (0.02%) | 399.9 V | 0.12 V (0.03%) | 0.6 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.06 V (0.01%) | 399.9 V | 0.09 V (0.02%) | 0.5 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 5 Ampere ved 120 Meter (400V)
Hvilket kabeltværsnit kræves til 5A ved 120 meter (400V)?
Til 5 Ampere over 120 meter ved 400V anbefales 2.5 mm² kobberkabel (spændingsfald 8.9V / 2.22%).
Hvor mange kW svarer 5A ved 400V til?
Det svarer til 3.46 kW med en anbefalet sikring på 6A.
Related Lengths & Currents (400V)
5A · 5m (400V)5A · 10m (400V)5A · 15m (400V)5A · 20m (400V)5A · 25m (400V)5A · 30m (400V)5A · 35m (400V)5A · 40m (400V)5A · 45m (400V)5A · 50m (400V)5A · 60m (400V)5A · 70m (400V)10A · 120m (400V)16A · 120m (400V)20A · 120m (400V)25A · 120m (400V)32A · 120m (400V)40A · 120m (400V)50A · 120m (400V)63A · 120m (400V)80A · 120m (400V)100A · 120m (400V)125A · 120m (400V)160A · 120m (400V)200A · 120m (400V)