⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 5 Ampere ved 40 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 5 A over 40 m ved 400V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 4.94V (1.24%)
Aluminum Cable (≤3% Drop)1.5 mm²Drop: 8.15V (2.04%)
Voltage at Load395.1 VLine Loss: 42.8 W
Max Power & Breaker3.46 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4.94 V (1.24%)395.1 V8.15 V (2.04%)42.8 W✓ OK (≤3%)
2.5 mm²24 A18 A2.97 V (0.74%)397.0 V4.89 V (1.22%)25.7 W✓ OK (≤3%)
4 mm²32 A25 A1.85 V (0.46%)398.1 V3.06 V (0.76%)16.1 W✓ OK (≤3%)
6 mm²41 A32 A1.24 V (0.31%)398.8 V2.04 V (0.51%)10.7 W✓ OK (≤3%)
10 mm²57 A44 A0.74 V (0.19%)399.3 V1.22 V (0.31%)6.4 W✓ OK (≤3%)
16 mm²76 A59 A0.46 V (0.12%)399.5 V0.76 V (0.19%)4.0 W✓ OK (≤3%)
25 mm²101 A78 A0.3 V (0.07%)399.7 V0.49 V (0.12%)2.6 W✓ OK (≤3%)
35 mm²125 A97 A0.21 V (0.05%)399.8 V0.35 V (0.09%)1.8 W✓ OK (≤3%)
50 mm²151 A118 A0.15 V (0.04%)399.9 V0.24 V (0.06%)1.3 W✓ OK (≤3%)
70 mm²192 A150 A0.11 V (0.03%)399.9 V0.17 V (0.04%)0.9 W✓ OK (≤3%)
95 mm²232 A181 A0.08 V (0.02%)399.9 V0.13 V (0.03%)0.7 W✓ OK (≤3%)
120 mm²269 A210 A0.06 V (0.02%)399.9 V0.1 V (0.03%)0.5 W✓ OK (≤3%)
150 mm²309 A241 A0.05 V (0.01%)400.0 V0.08 V (0.02%)0.4 W✓ OK (≤3%)
185 mm²353 A275 A0.04 V (0.01%)400.0 V0.07 V (0.02%)0.3 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.01%)400.0 V0.05 V (0.01%)0.3 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.01%)400.0 V0.04 V (0.01%)0.2 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.0%)400.0 V0.03 V (0.01%)0.2 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 5 Ampere ved 40 Meter (400V)

Hvilket kabeltværsnit kræves til 5A ved 40 meter (400V)?

Til 5 Ampere over 40 meter ved 400V anbefales 1.5 mm² kobberkabel (spændingsfald 4.94V / 1.24%).

Hvor mange kW svarer 5A ved 400V til?

Det svarer til 3.46 kW med en anbefalet sikring på 6A.