Kabeltværsnit for 5 Ampere ved 150 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 5 A over 150 m ved 230V.

Copper Cable (≤3% Drop)6 mm²Drop: 5.35V (2.33%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 5.29V (2.3%)
Voltage at Load224.7 VLine Loss: 26.8 W
Max Power & Breaker1.15 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A21.4 V (9.3%)208.6 V35.3 V (15.35%)107.0 WDrop High
2.5 mm²24 A18 A12.84 V (5.58%)217.2 V21.18 V (9.21%)64.2 WDrop High
4 mm²32 A25 A8.03 V (3.49%)222.0 V13.24 V (5.76%)40.1 W~ ≤5%
6 mm²41 A32 A5.35 V (2.33%)224.7 V8.82 V (3.84%)26.8 W✓ OK (≤3%)
10 mm²57 A44 A3.21 V (1.4%)226.8 V5.29 V (2.3%)16.1 W✓ OK (≤3%)
16 mm²76 A59 A2.01 V (0.87%)228.0 V3.31 V (1.44%)10.0 W✓ OK (≤3%)
25 mm²101 A78 A1.28 V (0.56%)228.7 V2.12 V (0.92%)6.4 W✓ OK (≤3%)
35 mm²125 A97 A0.92 V (0.4%)229.1 V1.51 V (0.66%)4.6 W✓ OK (≤3%)
50 mm²151 A118 A0.64 V (0.28%)229.4 V1.06 V (0.46%)3.2 W✓ OK (≤3%)
70 mm²192 A150 A0.46 V (0.2%)229.5 V0.76 V (0.33%)2.3 W✓ OK (≤3%)
95 mm²232 A181 A0.34 V (0.15%)229.7 V0.56 V (0.24%)1.7 W✓ OK (≤3%)
120 mm²269 A210 A0.27 V (0.12%)229.7 V0.44 V (0.19%)1.3 W✓ OK (≤3%)
150 mm²309 A241 A0.21 V (0.09%)229.8 V0.35 V (0.15%)1.1 W✓ OK (≤3%)
185 mm²353 A275 A0.17 V (0.08%)229.8 V0.29 V (0.12%)0.9 W✓ OK (≤3%)
240 mm²415 A324 A0.13 V (0.06%)229.9 V0.22 V (0.1%)0.7 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.05%)229.9 V0.18 V (0.08%)0.5 W✓ OK (≤3%)
400 mm²570 A445 A0.08 V (0.03%)229.9 V0.13 V (0.06%)0.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 5 Ampere ved 150 Meter (230V)

Hvilket kabeltværsnit kræves til 5A ved 150 meter (230V)?

Til 5 Ampere over 150 meter ved 230V anbefales 6 mm² kobberkabel (spændingsfald 5.35V / 2.33%).

Hvor mange kW svarer 5A ved 230V til?

Det svarer til 1.15 kW med en anbefalet sikring på 6A.