Kabeltværsnit for 5 Ampere ved 50 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 5 A over 50 m ved 230V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 4.28V (1.86%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 4.41V (1.92%)
Voltage at Load225.7 VLine Loss: 21.4 W
Max Power & Breaker1.15 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7.13 V (3.1%)222.9 V11.77 V (5.12%)35.7 W~ ≤5%
2.5 mm²24 A18 A4.28 V (1.86%)225.7 V7.06 V (3.07%)21.4 W✓ OK (≤3%)
4 mm²32 A25 A2.67 V (1.16%)227.3 V4.41 V (1.92%)13.4 W✓ OK (≤3%)
6 mm²41 A32 A1.78 V (0.78%)228.2 V2.94 V (1.28%)8.9 W✓ OK (≤3%)
10 mm²57 A44 A1.07 V (0.47%)228.9 V1.76 V (0.77%)5.3 W✓ OK (≤3%)
16 mm²76 A59 A0.67 V (0.29%)229.3 V1.1 V (0.48%)3.3 W✓ OK (≤3%)
25 mm²101 A78 A0.43 V (0.19%)229.6 V0.71 V (0.31%)2.1 W✓ OK (≤3%)
35 mm²125 A97 A0.31 V (0.13%)229.7 V0.5 V (0.22%)1.5 W✓ OK (≤3%)
50 mm²151 A118 A0.21 V (0.09%)229.8 V0.35 V (0.15%)1.1 W✓ OK (≤3%)
70 mm²192 A150 A0.15 V (0.07%)229.8 V0.25 V (0.11%)0.8 W✓ OK (≤3%)
95 mm²232 A181 A0.11 V (0.05%)229.9 V0.19 V (0.08%)0.6 W✓ OK (≤3%)
120 mm²269 A210 A0.09 V (0.04%)229.9 V0.15 V (0.06%)0.4 W✓ OK (≤3%)
150 mm²309 A241 A0.07 V (0.03%)229.9 V0.12 V (0.05%)0.4 W✓ OK (≤3%)
185 mm²353 A275 A0.06 V (0.03%)229.9 V0.1 V (0.04%)0.3 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.02%)230.0 V0.07 V (0.03%)0.2 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.02%)230.0 V0.06 V (0.03%)0.2 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.01%)230.0 V0.04 V (0.02%)0.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 5 Ampere ved 50 Meter (230V)

Hvilket kabeltværsnit kræves til 5A ved 50 meter (230V)?

Til 5 Ampere over 50 meter ved 230V anbefales 2.5 mm² kobberkabel (spændingsfald 4.28V / 1.86%).

Hvor mange kW svarer 5A ved 230V til?

Det svarer til 1.15 kW med en anbefalet sikring på 6A.