Kabeltværsnit for 5 Ampere ved 250 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 5 A over 250 m ved 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 5.35V (2.33%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.52V (2.4%)
Voltage at Load224.7 VLine Loss: 26.7 W
Max Power & Breaker1.15 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A35.67 V (15.51%)194.3 V58.83 V (25.58%)178.3 WDrop High
2.5 mm²24 A18 A21.4 V (9.3%)208.6 V35.3 V (15.35%)107.0 WDrop High
4 mm²32 A25 A13.38 V (5.82%)216.6 V22.06 V (9.59%)66.9 WDrop High
6 mm²41 A32 A8.92 V (3.88%)221.1 V14.71 V (6.39%)44.6 W~ ≤5%
10 mm²57 A44 A5.35 V (2.33%)224.7 V8.82 V (3.84%)26.7 W✓ OK (≤3%)
16 mm²76 A59 A3.34 V (1.45%)226.7 V5.52 V (2.4%)16.7 W✓ OK (≤3%)
25 mm²101 A78 A2.14 V (0.93%)227.9 V3.53 V (1.53%)10.7 W✓ OK (≤3%)
35 mm²125 A97 A1.53 V (0.66%)228.5 V2.52 V (1.1%)7.6 W✓ OK (≤3%)
50 mm²151 A118 A1.07 V (0.47%)228.9 V1.76 V (0.77%)5.3 W✓ OK (≤3%)
70 mm²192 A150 A0.76 V (0.33%)229.2 V1.26 V (0.55%)3.8 W✓ OK (≤3%)
95 mm²232 A181 A0.56 V (0.24%)229.4 V0.93 V (0.4%)2.8 W✓ OK (≤3%)
120 mm²269 A210 A0.45 V (0.19%)229.6 V0.74 V (0.32%)2.2 W✓ OK (≤3%)
150 mm²309 A241 A0.36 V (0.16%)229.6 V0.59 V (0.26%)1.8 W✓ OK (≤3%)
185 mm²353 A275 A0.29 V (0.13%)229.7 V0.48 V (0.21%)1.4 W✓ OK (≤3%)
240 mm²415 A324 A0.22 V (0.1%)229.8 V0.37 V (0.16%)1.1 W✓ OK (≤3%)
300 mm²477 A372 A0.18 V (0.08%)229.8 V0.29 V (0.13%)0.9 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.06%)229.9 V0.22 V (0.1%)0.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 5 Ampere ved 250 Meter (230V)

Hvilket kabeltværsnit kræves til 5A ved 250 meter (230V)?

Til 5 Ampere over 250 meter ved 230V anbefales 10 mm² kobberkabel (spændingsfald 5.35V / 2.33%).

Hvor mange kW svarer 5A ved 230V til?

Det svarer til 1.15 kW med en anbefalet sikring på 6A.