Kabeltværsnit for 20 Ampere ved 50 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 20 A over 50 m ved 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 4.28V (1.86%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 4.41V (1.92%)
Voltage at Load225.7 VLine Loss: 85.6 W
Max Power & Breaker4.6 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A28.53 V (12.41%)201.5 V47.07 V (20.46%)570.7 WDrop High
2.5 mm²24 A18 A17.12 V (7.44%)212.9 V28.24 V (12.28%)342.4 WDrop High
4 mm²32 A25 A10.7 V (4.65%)219.3 V17.65 V (7.67%)214.0 W~ ≤5%
6 mm²41 A32 A7.13 V (3.1%)222.9 V11.77 V (5.12%)142.7 W~ ≤5%
10 mm²57 A44 A4.28 V (1.86%)225.7 V7.06 V (3.07%)85.6 W✓ OK (≤3%)
16 mm²76 A59 A2.67 V (1.16%)227.3 V4.41 V (1.92%)53.5 W✓ OK (≤3%)
25 mm²101 A78 A1.71 V (0.74%)228.3 V2.82 V (1.23%)34.2 W✓ OK (≤3%)
35 mm²125 A97 A1.22 V (0.53%)228.8 V2.02 V (0.88%)24.5 W✓ OK (≤3%)
50 mm²151 A118 A0.86 V (0.37%)229.1 V1.41 V (0.61%)17.1 W✓ OK (≤3%)
70 mm²192 A150 A0.61 V (0.27%)229.4 V1.01 V (0.44%)12.2 W✓ OK (≤3%)
95 mm²232 A181 A0.45 V (0.2%)229.5 V0.74 V (0.32%)9.0 W✓ OK (≤3%)
120 mm²269 A210 A0.36 V (0.16%)229.6 V0.59 V (0.26%)7.1 W✓ OK (≤3%)
150 mm²309 A241 A0.29 V (0.12%)229.7 V0.47 V (0.2%)5.7 W✓ OK (≤3%)
185 mm²353 A275 A0.23 V (0.1%)229.8 V0.38 V (0.17%)4.6 W✓ OK (≤3%)
240 mm²415 A324 A0.18 V (0.08%)229.8 V0.29 V (0.13%)3.6 W✓ OK (≤3%)
300 mm²477 A372 A0.14 V (0.06%)229.9 V0.24 V (0.1%)2.9 W✓ OK (≤3%)
400 mm²570 A445 A0.11 V (0.05%)229.9 V0.18 V (0.08%)2.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 20 Ampere ved 50 Meter (230V)

Hvilket kabeltværsnit kræves til 20A ved 50 meter (230V)?

Til 20 Ampere over 50 meter ved 230V anbefales 10 mm² kobberkabel (spændingsfald 4.28V / 1.86%).

Hvor mange kW svarer 20A ved 230V til?

Det svarer til 4.6 kW med en anbefalet sikring på 20A.