Kabeltværsnit for 500 Ampere ved 35 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 500 A over 35 m ved 230V.
Copper Cable (≤3% Drop)400 mm²Drop: 1.87V (0.81%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.09V (1.34%)
Voltage at Load228.1 VLine Loss: 936.2 W
Max Power & Breaker115.0 kW500A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 499.33 V (217.1%) | 0.0 V | 823.67 V (358.12%) | 249666.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 299.6 V (130.26%) | 0.0 V | 494.2 V (214.87%) | 149800.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 187.25 V (81.41%) | 42.8 V | 308.88 V (134.29%) | 93625.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 124.83 V (54.28%) | 105.2 V | 205.92 V (89.53%) | 62416.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 74.9 V (32.57%) | 155.1 V | 123.55 V (53.72%) | 37450.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 46.81 V (20.35%) | 183.2 V | 77.22 V (33.57%) | 23406.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 29.96 V (13.03%) | 200.0 V | 49.42 V (21.49%) | 14980.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 21.4 V (9.3%) | 208.6 V | 35.3 V (15.35%) | 10700.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 14.98 V (6.51%) | 215.0 V | 24.71 V (10.74%) | 7490.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 10.7 V (4.65%) | 219.3 V | 17.65 V (7.67%) | 5350.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 7.88 V (3.43%) | 222.1 V | 13.01 V (5.65%) | 3942.1 W | Drop High |
| 120 mm² | 269 A | 210 A | 6.24 V (2.71%) | 223.8 V | 10.3 V (4.48%) | 3120.8 W | Drop High |
| 150 mm² | 309 A | 241 A | 4.99 V (2.17%) | 225.0 V | 8.24 V (3.58%) | 2496.7 W | Drop High |
| 185 mm² | 353 A | 275 A | 4.05 V (1.76%) | 226.0 V | 6.68 V (2.9%) | 2024.3 W | Drop High |
| 240 mm² | 415 A | 324 A | 3.12 V (1.36%) | 226.9 V | 5.15 V (2.24%) | 1560.4 W | Drop High |
| 300 mm² | 477 A | 372 A | 2.5 V (1.09%) | 227.5 V | 4.12 V (1.79%) | 1248.3 W | Drop High |
| 400 mm² | 570 A | 445 A | 1.87 V (0.81%) | 228.1 V | 3.09 V (1.34%) | 936.2 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 500 Ampere ved 35 Meter (230V)
Hvilket kabeltværsnit kræves til 500A ved 35 meter (230V)?
Til 500 Ampere over 35 meter ved 230V anbefales 400 mm² kobberkabel (spændingsfald 1.87V / 0.81%).
Hvor mange kW svarer 500A ved 230V til?
Det svarer til 115.0 kW med en anbefalet sikring på 500A.
Related Lengths & Currents (230V)
500A · 5m (230V)500A · 10m (230V)500A · 15m (230V)500A · 20m (230V)500A · 25m (230V)500A · 30m (230V)500A · 40m (230V)500A · 45m (230V)500A · 50m (230V)500A · 60m (230V)500A · 70m (230V)10A · 35m (230V)16A · 35m (230V)20A · 35m (230V)25A · 35m (230V)32A · 35m (230V)40A · 35m (230V)50A · 35m (230V)63A · 35m (230V)80A · 35m (230V)100A · 35m (230V)125A · 35m (230V)160A · 35m (230V)200A · 35m (230V)