Kabeltværsnit for 500 Ampere ved 70 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 500 A over 70 m ved 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 3.75V (1.63%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.18V (2.69%)
Voltage at Load226.3 VLine Loss: 1872.5 W
Max Power & Breaker115.0 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A998.67 V (434.2%)0.0 V1647.33 V (716.23%)499333.3 WDrop High
2.5 mm²24 A18 A599.2 V (260.52%)0.0 V988.4 V (429.74%)299600.0 WDrop High
4 mm²32 A25 A374.5 V (162.83%)0.0 V617.75 V (268.59%)187250.0 WDrop High
6 mm²41 A32 A249.67 V (108.55%)0.0 V411.83 V (179.06%)124833.3 WDrop High
10 mm²57 A44 A149.8 V (65.13%)80.2 V247.1 V (107.43%)74900.0 WDrop High
16 mm²76 A59 A93.62 V (40.71%)136.4 V154.44 V (67.15%)46812.5 WDrop High
25 mm²101 A78 A59.92 V (26.05%)170.1 V98.84 V (42.97%)29960.0 WDrop High
35 mm²125 A97 A42.8 V (18.61%)187.2 V70.6 V (30.7%)21400.0 WDrop High
50 mm²151 A118 A29.96 V (13.03%)200.0 V49.42 V (21.49%)14980.0 WDrop High
70 mm²192 A150 A21.4 V (9.3%)208.6 V35.3 V (15.35%)10700.0 WDrop High
95 mm²232 A181 A15.77 V (6.86%)214.2 V26.01 V (11.31%)7884.2 WDrop High
120 mm²269 A210 A12.48 V (5.43%)217.5 V20.59 V (8.95%)6241.7 WDrop High
150 mm²309 A241 A9.99 V (4.34%)220.0 V16.47 V (7.16%)4993.3 WDrop High
185 mm²353 A275 A8.1 V (3.52%)221.9 V13.36 V (5.81%)4048.6 WDrop High
240 mm²415 A324 A6.24 V (2.71%)223.8 V10.3 V (4.48%)3120.8 WDrop High
300 mm²477 A372 A4.99 V (2.17%)225.0 V8.24 V (3.58%)2496.7 WDrop High
400 mm²570 A445 A3.75 V (1.63%)226.3 V6.18 V (2.69%)1872.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 500 Ampere ved 70 Meter (230V)

Hvilket kabeltværsnit kræves til 500A ved 70 meter (230V)?

Til 500 Ampere over 70 meter ved 230V anbefales 400 mm² kobberkabel (spændingsfald 3.75V / 1.63%).

Hvor mange kW svarer 500A ved 230V til?

Det svarer til 115.0 kW med en anbefalet sikring på 500A.