Kabeltværsnit for 550 Ampere ved 50 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 550 A over 50 m ved 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 2.94V (1.28%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.85V (2.11%)
Voltage at Load227.1 VLine Loss: 1618.4 W
Max Power & Breaker126.5 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A784.67 V (341.16%)0.0 V1294.33 V (562.75%)431566.7 WDrop High
2.5 mm²24 A18 A470.8 V (204.7%)0.0 V776.6 V (337.65%)258940.0 WDrop High
4 mm²32 A25 A294.25 V (127.93%)0.0 V485.38 V (211.03%)161837.5 WDrop High
6 mm²41 A32 A196.17 V (85.29%)33.8 V323.58 V (140.69%)107891.7 WDrop High
10 mm²57 A44 A117.7 V (51.17%)112.3 V194.15 V (84.41%)64735.0 WDrop High
16 mm²76 A59 A73.56 V (31.98%)156.4 V121.34 V (52.76%)40459.4 WDrop High
25 mm²101 A78 A47.08 V (20.47%)182.9 V77.66 V (33.77%)25894.0 WDrop High
35 mm²125 A97 A33.63 V (14.62%)196.4 V55.47 V (24.12%)18495.7 WDrop High
50 mm²151 A118 A23.54 V (10.23%)206.5 V38.83 V (16.88%)12947.0 WDrop High
70 mm²192 A150 A16.81 V (7.31%)213.2 V27.74 V (12.06%)9247.9 WDrop High
95 mm²232 A181 A12.39 V (5.39%)217.6 V20.44 V (8.89%)6814.2 WDrop High
120 mm²269 A210 A9.81 V (4.26%)220.2 V16.18 V (7.03%)5394.6 WDrop High
150 mm²309 A241 A7.85 V (3.41%)222.2 V12.94 V (5.63%)4315.7 WDrop High
185 mm²353 A275 A6.36 V (2.77%)223.6 V10.49 V (4.56%)3499.2 WDrop High
240 mm²415 A324 A4.9 V (2.13%)225.1 V8.09 V (3.52%)2697.3 WDrop High
300 mm²477 A372 A3.92 V (1.71%)226.1 V6.47 V (2.81%)2157.8 WDrop High
400 mm²570 A445 A2.94 V (1.28%)227.1 V4.85 V (2.11%)1618.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 550 Ampere ved 50 Meter (230V)

Hvilket kabeltværsnit kræves til 550A ved 50 meter (230V)?

Til 550 Ampere over 50 meter ved 230V anbefales 400 mm² kobberkabel (spændingsfald 2.94V / 1.28%).

Hvor mange kW svarer 550A ved 230V til?

Det svarer til 126.5 kW med en anbefalet sikring på 600A.