Kabeltværsnit for 63 Ampere ved 20 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 63 A over 20 m ved 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 2.92V (0.73%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 3.08V (0.77%)
Voltage at Load397.1 VLine Loss: 318.5 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A31.14 V (7.78%)368.9 V51.36 V (12.84%)3397.5 WDrop High
2.5 mm²24 A18 A18.68 V (4.67%)381.3 V30.82 V (7.7%)2038.5 WDrop High
4 mm²32 A25 A11.68 V (2.92%)388.3 V19.26 V (4.81%)1274.0 WDrop High
6 mm²41 A32 A7.78 V (1.95%)392.2 V12.84 V (3.21%)849.4 WDrop High
10 mm²57 A44 A4.67 V (1.17%)395.3 V7.7 V (1.93%)509.6 WDrop High
16 mm²76 A59 A2.92 V (0.73%)397.1 V4.81 V (1.2%)318.5 W✓ OK (≤3%)
25 mm²101 A78 A1.87 V (0.47%)398.1 V3.08 V (0.77%)203.8 W✓ OK (≤3%)
35 mm²125 A97 A1.33 V (0.33%)398.7 V2.2 V (0.55%)145.6 W✓ OK (≤3%)
50 mm²151 A118 A0.93 V (0.23%)399.1 V1.54 V (0.39%)101.9 W✓ OK (≤3%)
70 mm²192 A150 A0.67 V (0.17%)399.3 V1.1 V (0.28%)72.8 W✓ OK (≤3%)
95 mm²232 A181 A0.49 V (0.12%)399.5 V0.81 V (0.2%)53.6 W✓ OK (≤3%)
120 mm²269 A210 A0.39 V (0.1%)399.6 V0.64 V (0.16%)42.5 W✓ OK (≤3%)
150 mm²309 A241 A0.31 V (0.08%)399.7 V0.51 V (0.13%)34.0 W✓ OK (≤3%)
185 mm²353 A275 A0.25 V (0.06%)399.7 V0.42 V (0.1%)27.5 W✓ OK (≤3%)
240 mm²415 A324 A0.19 V (0.05%)399.8 V0.32 V (0.08%)21.2 W✓ OK (≤3%)
300 mm²477 A372 A0.16 V (0.04%)399.8 V0.26 V (0.06%)17.0 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.03%)399.9 V0.19 V (0.05%)12.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 63 Ampere ved 20 Meter (400V)

Hvilket kabeltværsnit kræves til 63A ved 20 meter (400V)?

Til 63 Ampere over 20 meter ved 400V anbefales 16 mm² kobberkabel (spændingsfald 2.92V / 0.73%).

Hvor mange kW svarer 63A ved 400V til?

Det svarer til 43.65 kW med en anbefalet sikring på 63A.