Kabeltværsnit for 63 Ampere ved 50 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 63 A over 50 m ved 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 7.3V (1.82%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 7.7V (1.93%)
Voltage at Load392.7 VLine Loss: 796.3 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A77.84 V (19.46%)322.2 V128.4 V (32.1%)8493.7 WDrop High
2.5 mm²24 A18 A46.7 V (11.68%)353.3 V77.04 V (19.26%)5096.2 WDrop High
4 mm²32 A25 A29.19 V (7.3%)370.8 V48.15 V (12.04%)3185.1 WDrop High
6 mm²41 A32 A19.46 V (4.86%)380.5 V32.1 V (8.02%)2123.4 WDrop High
10 mm²57 A44 A11.68 V (2.92%)388.3 V19.26 V (4.81%)1274.0 WDrop High
16 mm²76 A59 A7.3 V (1.82%)392.7 V12.04 V (3.01%)796.3 W✓ OK (≤3%)
25 mm²101 A78 A4.67 V (1.17%)395.3 V7.7 V (1.93%)509.6 W✓ OK (≤3%)
35 mm²125 A97 A3.34 V (0.83%)396.7 V5.5 V (1.38%)364.0 W✓ OK (≤3%)
50 mm²151 A118 A2.34 V (0.58%)397.7 V3.85 V (0.96%)254.8 W✓ OK (≤3%)
70 mm²192 A150 A1.67 V (0.42%)398.3 V2.75 V (0.69%)182.0 W✓ OK (≤3%)
95 mm²232 A181 A1.23 V (0.31%)398.8 V2.03 V (0.51%)134.1 W✓ OK (≤3%)
120 mm²269 A210 A0.97 V (0.24%)399.0 V1.6 V (0.4%)106.2 W✓ OK (≤3%)
150 mm²309 A241 A0.78 V (0.19%)399.2 V1.28 V (0.32%)84.9 W✓ OK (≤3%)
185 mm²353 A275 A0.63 V (0.16%)399.4 V1.04 V (0.26%)68.9 W✓ OK (≤3%)
240 mm²415 A324 A0.49 V (0.12%)399.5 V0.8 V (0.2%)53.1 W✓ OK (≤3%)
300 mm²477 A372 A0.39 V (0.1%)399.6 V0.64 V (0.16%)42.5 W✓ OK (≤3%)
400 mm²570 A445 A0.29 V (0.07%)399.7 V0.48 V (0.12%)31.9 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 63 Ampere ved 50 Meter (400V)

Hvilket kabeltværsnit kræves til 63A ved 50 meter (400V)?

Til 63 Ampere over 50 meter ved 400V anbefales 16 mm² kobberkabel (spændingsfald 7.3V / 1.82%).

Hvor mange kW svarer 63A ved 400V til?

Det svarer til 43.65 kW med en anbefalet sikring på 63A.