Kabeltværsnit for 63 Ampere ved 90 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 63 A over 90 m ved 230V.

Copper Cable (≤3% Drop)50 mm²Drop: 4.85V (2.11%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 5.72V (2.49%)
Voltage at Load225.1 VLine Loss: 305.8 W
Max Power & Breaker14.49 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A161.78 V (70.34%)68.2 V266.87 V (116.03%)10192.4 WDrop High
2.5 mm²24 A18 A97.07 V (42.2%)132.9 V160.12 V (69.62%)6115.4 WDrop High
4 mm²32 A25 A60.67 V (26.38%)169.3 V100.08 V (43.51%)3822.1 WDrop High
6 mm²41 A32 A40.45 V (17.59%)189.6 V66.72 V (29.01%)2548.1 WDrop High
10 mm²57 A44 A24.27 V (10.55%)205.7 V40.03 V (17.4%)1528.9 WDrop High
16 mm²76 A59 A15.17 V (6.59%)214.8 V25.02 V (10.88%)955.5 WDrop High
25 mm²101 A78 A9.71 V (4.22%)220.3 V16.01 V (6.96%)611.5 W~ ≤5%
35 mm²125 A97 A6.93 V (3.01%)223.1 V11.44 V (4.97%)436.8 W~ ≤5%
50 mm²151 A118 A4.85 V (2.11%)225.1 V8.01 V (3.48%)305.8 W✓ OK (≤3%)
70 mm²192 A150 A3.47 V (1.51%)226.5 V5.72 V (2.49%)218.4 W✓ OK (≤3%)
95 mm²232 A181 A2.55 V (1.11%)227.4 V4.21 V (1.83%)160.9 W✓ OK (≤3%)
120 mm²269 A210 A2.02 V (0.88%)228.0 V3.34 V (1.45%)127.4 W✓ OK (≤3%)
150 mm²309 A241 A1.62 V (0.7%)228.4 V2.67 V (1.16%)101.9 W✓ OK (≤3%)
185 mm²353 A275 A1.31 V (0.57%)228.7 V2.16 V (0.94%)82.6 W✓ OK (≤3%)
240 mm²415 A324 A1.01 V (0.44%)229.0 V1.67 V (0.73%)63.7 W✓ OK (≤3%)
300 mm²477 A372 A0.81 V (0.35%)229.2 V1.33 V (0.58%)51.0 W✓ OK (≤3%)
400 mm²570 A445 A0.61 V (0.26%)229.4 V1.0 V (0.44%)38.2 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 63 Ampere ved 90 Meter (230V)

Hvilket kabeltværsnit kræves til 63A ved 90 meter (230V)?

Til 63 Ampere over 90 meter ved 230V anbefales 50 mm² kobberkabel (spændingsfald 4.85V / 2.11%).

Hvor mange kW svarer 63A ved 230V til?

Det svarer til 14.49 kW med en anbefalet sikring på 63A.