Kabeltværsnit for 160 Ampere ved 90 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 160 A over 90 m ved 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 6.49V (2.82%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 6.78V (2.95%)
Voltage at Load223.5 VLine Loss: 1038.0 W
Max Power & Breaker36.8 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A410.88 V (178.64%)0.0 V677.76 V (294.68%)65740.8 WDrop High
2.5 mm²24 A18 A246.53 V (107.19%)0.0 V406.66 V (176.81%)39444.5 WDrop High
4 mm²32 A25 A154.08 V (66.99%)75.9 V254.16 V (110.5%)24652.8 WDrop High
6 mm²41 A32 A102.72 V (44.66%)127.3 V169.44 V (73.67%)16435.2 WDrop High
10 mm²57 A44 A61.63 V (26.8%)168.4 V101.66 V (44.2%)9861.1 WDrop High
16 mm²76 A59 A38.52 V (16.75%)191.5 V63.54 V (27.63%)6163.2 WDrop High
25 mm²101 A78 A24.65 V (10.72%)205.3 V40.67 V (17.68%)3944.4 WDrop High
35 mm²125 A97 A17.61 V (7.66%)212.4 V29.05 V (12.63%)2817.5 WDrop High
50 mm²151 A118 A12.33 V (5.36%)217.7 V20.33 V (8.84%)1972.2 WDrop High
70 mm²192 A150 A8.8 V (3.83%)221.2 V14.52 V (6.31%)1408.7 W~ ≤5%
95 mm²232 A181 A6.49 V (2.82%)223.5 V10.7 V (4.65%)1038.0 W✓ OK (≤3%)
120 mm²269 A210 A5.14 V (2.23%)224.9 V8.47 V (3.68%)821.8 W✓ OK (≤3%)
150 mm²309 A241 A4.11 V (1.79%)225.9 V6.78 V (2.95%)657.4 W✓ OK (≤3%)
185 mm²353 A275 A3.33 V (1.45%)226.7 V5.5 V (2.39%)533.0 W✓ OK (≤3%)
240 mm²415 A324 A2.57 V (1.12%)227.4 V4.24 V (1.84%)410.9 W✓ OK (≤3%)
300 mm²477 A372 A2.05 V (0.89%)227.9 V3.39 V (1.47%)328.7 W✓ OK (≤3%)
400 mm²570 A445 A1.54 V (0.67%)228.5 V2.54 V (1.11%)246.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 160 Ampere ved 90 Meter (230V)

Hvilket kabeltværsnit kræves til 160A ved 90 meter (230V)?

Til 160 Ampere over 90 meter ved 230V anbefales 95 mm² kobberkabel (spændingsfald 6.49V / 2.82%).

Hvor mange kW svarer 160A ved 230V til?

Det svarer til 36.8 kW med en anbefalet sikring på 160A.