Kabeltværsnit for 70 Ampere ved 10 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 70 A over 10 m ved 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 1.62V (0.41%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 1.71V (0.43%)
Voltage at Load398.4 VLine Loss: 196.6 W
Max Power & Breaker48.5 kW70A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 70A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A17.3 V (4.32%)382.7 V28.53 V (7.13%)2097.2 WDrop High
2.5 mm²24 A18 A10.38 V (2.59%)389.6 V17.12 V (4.28%)1258.3 WDrop High
4 mm²32 A25 A6.49 V (1.62%)393.5 V10.7 V (2.67%)786.4 WDrop High
6 mm²41 A32 A4.32 V (1.08%)395.7 V7.13 V (1.78%)524.3 WDrop High
10 mm²57 A44 A2.59 V (0.65%)397.4 V4.28 V (1.07%)314.6 WDrop High
16 mm²76 A59 A1.62 V (0.41%)398.4 V2.67 V (0.67%)196.6 W✓ OK (≤3%)
25 mm²101 A78 A1.04 V (0.26%)399.0 V1.71 V (0.43%)125.8 W✓ OK (≤3%)
35 mm²125 A97 A0.74 V (0.19%)399.3 V1.22 V (0.31%)89.9 W✓ OK (≤3%)
50 mm²151 A118 A0.52 V (0.13%)399.5 V0.86 V (0.21%)62.9 W✓ OK (≤3%)
70 mm²192 A150 A0.37 V (0.09%)399.6 V0.61 V (0.15%)44.9 W✓ OK (≤3%)
95 mm²232 A181 A0.27 V (0.07%)399.7 V0.45 V (0.11%)33.1 W✓ OK (≤3%)
120 mm²269 A210 A0.22 V (0.05%)399.8 V0.36 V (0.09%)26.2 W✓ OK (≤3%)
150 mm²309 A241 A0.17 V (0.04%)399.8 V0.29 V (0.07%)21.0 W✓ OK (≤3%)
185 mm²353 A275 A0.14 V (0.04%)399.9 V0.23 V (0.06%)17.0 W✓ OK (≤3%)
240 mm²415 A324 A0.11 V (0.03%)399.9 V0.18 V (0.04%)13.1 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.02%)399.9 V0.14 V (0.04%)10.5 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.02%)399.9 V0.11 V (0.03%)7.9 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 70 Ampere ved 10 Meter (400V)

Hvilket kabeltværsnit kræves til 70A ved 10 meter (400V)?

Til 70 Ampere over 10 meter ved 400V anbefales 16 mm² kobberkabel (spændingsfald 1.62V / 0.41%).

Hvor mange kW svarer 70A ved 400V til?

Det svarer til 48.5 kW med en anbefalet sikring på 70A.