Kabeltværsnit for 700 Ampere ved 100 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 700 A over 100 m ved 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.25V (0.81%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.7V (2.67%)
Voltage at Load396.8 VLine Loss: 3932.2 W
Max Power & Breaker484.97 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1729.74 V (432.44%)0.0 V2853.27 V (713.32%)2097200.0 WDrop High
2.5 mm²24 A18 A1037.84 V (259.46%)0.0 V1711.96 V (427.99%)1258320.0 WDrop High
4 mm²32 A25 A648.65 V (162.16%)0.0 V1069.97 V (267.49%)786450.0 WDrop High
6 mm²41 A32 A432.44 V (108.11%)0.0 V713.32 V (178.33%)524300.0 WDrop High
10 mm²57 A44 A259.46 V (64.87%)140.5 V427.99 V (107.0%)314580.0 WDrop High
16 mm²76 A59 A162.16 V (40.54%)237.8 V267.49 V (66.87%)196612.5 WDrop High
25 mm²101 A78 A103.78 V (25.95%)296.2 V171.2 V (42.8%)125832.0 WDrop High
35 mm²125 A97 A74.13 V (18.53%)325.9 V122.28 V (30.57%)89880.0 WDrop High
50 mm²151 A118 A51.89 V (12.97%)348.1 V85.6 V (21.4%)62916.0 WDrop High
70 mm²192 A150 A37.07 V (9.27%)362.9 V61.14 V (15.29%)44940.0 WDrop High
95 mm²232 A181 A27.31 V (6.83%)372.7 V45.05 V (11.26%)33113.7 WDrop High
120 mm²269 A210 A21.62 V (5.41%)378.4 V35.67 V (8.92%)26215.0 WDrop High
150 mm²309 A241 A17.3 V (4.32%)382.7 V28.53 V (7.13%)20972.0 WDrop High
185 mm²353 A275 A14.02 V (3.51%)386.0 V23.13 V (5.78%)17004.3 WDrop High
240 mm²415 A324 A10.81 V (2.7%)389.2 V17.83 V (4.46%)13107.5 WDrop High
300 mm²477 A372 A8.65 V (2.16%)391.4 V14.27 V (3.57%)10486.0 WDrop High
400 mm²570 A445 A6.49 V (1.62%)393.5 V10.7 V (2.67%)7864.5 WDrop High

FAQ — Kabeltværsnit for 700 Ampere ved 100 Meter (400V)

Hvilket kabeltværsnit kræves til 700A ved 100 meter (400V)?

Til 700 Ampere over 100 meter ved 400V anbefales 2× 400 mm² kobberkabel (spændingsfald 3.25V / 0.81%).

Hvor mange kW svarer 700A ved 400V til?

Det svarer til 484.97 kW med en anbefalet sikring på 700A.