Kabeltværsnit for 32 Ampere ved 100 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 32 A over 100 m ved 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 11.86V (2.97%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 7.83V (1.96%)
Voltage at Load388.1 VLine Loss: 657.4 W
Max Power & Breaker22.17 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A79.07 V (19.77%)320.9 V130.43 V (32.61%)4382.7 WDrop High
2.5 mm²24 A18 A47.44 V (11.86%)352.6 V78.26 V (19.57%)2629.6 WDrop High
4 mm²32 A25 A29.65 V (7.41%)370.3 V48.91 V (12.23%)1643.5 WDrop High
6 mm²41 A32 A19.77 V (4.94%)380.2 V32.61 V (8.15%)1095.7 W~ ≤5%
10 mm²57 A44 A11.86 V (2.97%)388.1 V19.57 V (4.89%)657.4 W✓ OK (≤3%)
16 mm²76 A59 A7.41 V (1.85%)392.6 V12.23 V (3.06%)410.9 W✓ OK (≤3%)
25 mm²101 A78 A4.74 V (1.19%)395.3 V7.83 V (1.96%)263.0 W✓ OK (≤3%)
35 mm²125 A97 A3.39 V (0.85%)396.6 V5.59 V (1.4%)187.8 W✓ OK (≤3%)
50 mm²151 A118 A2.37 V (0.59%)397.6 V3.91 V (0.98%)131.5 W✓ OK (≤3%)
70 mm²192 A150 A1.69 V (0.42%)398.3 V2.8 V (0.7%)93.9 W✓ OK (≤3%)
95 mm²232 A181 A1.25 V (0.31%)398.8 V2.06 V (0.51%)69.2 W✓ OK (≤3%)
120 mm²269 A210 A0.99 V (0.25%)399.0 V1.63 V (0.41%)54.8 W✓ OK (≤3%)
150 mm²309 A241 A0.79 V (0.2%)399.2 V1.3 V (0.33%)43.8 W✓ OK (≤3%)
185 mm²353 A275 A0.64 V (0.16%)399.4 V1.06 V (0.26%)35.5 W✓ OK (≤3%)
240 mm²415 A324 A0.49 V (0.12%)399.5 V0.82 V (0.2%)27.4 W✓ OK (≤3%)
300 mm²477 A372 A0.4 V (0.1%)399.6 V0.65 V (0.16%)21.9 W✓ OK (≤3%)
400 mm²570 A445 A0.3 V (0.07%)399.7 V0.49 V (0.12%)16.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 32 Ampere ved 100 Meter (400V)

Hvilket kabeltværsnit kræves til 32A ved 100 meter (400V)?

Til 32 Ampere over 100 meter ved 400V anbefales 10 mm² kobberkabel (spændingsfald 11.86V / 2.97%).

Hvor mange kW svarer 32A ved 400V til?

Det svarer til 22.17 kW med en anbefalet sikring på 32A.