Kabeltværsnit for 750 Ampere ved 250 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 750 A over 250 m ved 400V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 8.69V (2.17%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 28.66V (7.17%)
Voltage at Load391.3 VLine Loss: 11285.1 W
Max Power & Breaker519.62 kW800A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 250m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 4633.24 V (1158.31%) | 0.0 V | 7642.67 V (1910.67%) | 6018750.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 2779.94 V (694.99%) | 0.0 V | 4585.6 V (1146.4%) | 3611250.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1737.46 V (434.37%) | 0.0 V | 2866.0 V (716.5%) | 2257031.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 1158.31 V (289.58%) | 0.0 V | 1910.67 V (477.67%) | 1504687.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 694.99 V (173.75%) | 0.0 V | 1146.4 V (286.6%) | 902812.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 434.37 V (108.59%) | 0.0 V | 716.5 V (179.13%) | 564257.8 W | Drop High |
| 25 mm² | 101 A | 78 A | 277.99 V (69.5%) | 122.0 V | 458.56 V (114.64%) | 361125.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 198.57 V (49.64%) | 201.4 V | 327.54 V (81.89%) | 257946.4 W | Drop High |
| 50 mm² | 151 A | 118 A | 139.0 V (34.75%) | 261.0 V | 229.28 V (57.32%) | 180562.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 99.28 V (24.82%) | 300.7 V | 163.77 V (40.94%) | 128973.2 W | Drop High |
| 95 mm² | 232 A | 181 A | 73.16 V (18.29%) | 326.8 V | 120.67 V (30.17%) | 95032.9 W | Drop High |
| 120 mm² | 269 A | 210 A | 57.92 V (14.48%) | 342.1 V | 95.53 V (23.88%) | 75234.4 W | Drop High |
| 150 mm² | 309 A | 241 A | 46.33 V (11.58%) | 353.7 V | 76.43 V (19.11%) | 60187.5 W | Drop High |
| 185 mm² | 353 A | 275 A | 37.57 V (9.39%) | 362.4 V | 61.97 V (15.49%) | 48800.7 W | Drop High |
| 240 mm² | 415 A | 324 A | 28.96 V (7.24%) | 371.0 V | 47.77 V (11.94%) | 37617.2 W | Drop High |
| 300 mm² | 477 A | 372 A | 23.17 V (5.79%) | 376.8 V | 38.21 V (9.55%) | 30093.8 W | Drop High |
| 400 mm² | 570 A | 445 A | 17.37 V (4.34%) | 382.6 V | 28.66 V (7.17%) | 22570.3 W | Drop High |
FAQ — Kabeltværsnit for 750 Ampere ved 250 Meter (400V)
Hvilket kabeltværsnit kræves til 750A ved 250 meter (400V)?
Til 750 Ampere over 250 meter ved 400V anbefales 2× 400 mm² kobberkabel (spændingsfald 8.69V / 2.17%).
Hvor mange kW svarer 750A ved 400V til?
Det svarer til 519.62 kW med en anbefalet sikring på 800A.
Related Lengths & Currents (400V)
750A · 5m (400V)750A · 10m (400V)750A · 15m (400V)750A · 20m (400V)750A · 25m (400V)750A · 30m (400V)750A · 35m (400V)750A · 40m (400V)750A · 45m (400V)750A · 50m (400V)750A · 60m (400V)750A · 70m (400V)10A · 250m (400V)16A · 250m (400V)20A · 250m (400V)25A · 250m (400V)32A · 250m (400V)40A · 250m (400V)50A · 250m (400V)63A · 250m (400V)80A · 250m (400V)100A · 250m (400V)125A · 250m (400V)160A · 250m (400V)200A · 250m (400V)