Kabeltværsnit for 90 Ampere ved 30 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 90 A over 30 m ved 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 4.62V (2.01%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 5.45V (2.37%)
Voltage at Load225.4 VLine Loss: 416.0 W
Max Power & Breaker20.7 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A77.04 V (33.5%)153.0 V127.08 V (55.25%)6933.6 WDrop High
2.5 mm²24 A18 A46.22 V (20.1%)183.8 V76.25 V (33.15%)4160.2 WDrop High
4 mm²32 A25 A28.89 V (12.56%)201.1 V47.65 V (20.72%)2600.1 WDrop High
6 mm²41 A32 A19.26 V (8.37%)210.7 V31.77 V (13.81%)1733.4 WDrop High
10 mm²57 A44 A11.56 V (5.02%)218.4 V19.06 V (8.29%)1040.0 WDrop High
16 mm²76 A59 A7.22 V (3.14%)222.8 V11.91 V (5.18%)650.0 WDrop High
25 mm²101 A78 A4.62 V (2.01%)225.4 V7.62 V (3.32%)416.0 W✓ OK (≤3%)
35 mm²125 A97 A3.3 V (1.44%)226.7 V5.45 V (2.37%)297.2 W✓ OK (≤3%)
50 mm²151 A118 A2.31 V (1.0%)227.7 V3.81 V (1.66%)208.0 W✓ OK (≤3%)
70 mm²192 A150 A1.65 V (0.72%)228.3 V2.72 V (1.18%)148.6 W✓ OK (≤3%)
95 mm²232 A181 A1.22 V (0.53%)228.8 V2.01 V (0.87%)109.5 W✓ OK (≤3%)
120 mm²269 A210 A0.96 V (0.42%)229.0 V1.59 V (0.69%)86.7 W✓ OK (≤3%)
150 mm²309 A241 A0.77 V (0.33%)229.2 V1.27 V (0.55%)69.3 W✓ OK (≤3%)
185 mm²353 A275 A0.62 V (0.27%)229.4 V1.03 V (0.45%)56.2 W✓ OK (≤3%)
240 mm²415 A324 A0.48 V (0.21%)229.5 V0.79 V (0.35%)43.3 W✓ OK (≤3%)
300 mm²477 A372 A0.39 V (0.17%)229.6 V0.64 V (0.28%)34.7 W✓ OK (≤3%)
400 mm²570 A445 A0.29 V (0.13%)229.7 V0.48 V (0.21%)26.0 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 90 Ampere ved 30 Meter (230V)

Hvilket kabeltværsnit kræves til 90A ved 30 meter (230V)?

Til 90 Ampere over 30 meter ved 230V anbefales 25 mm² kobberkabel (spændingsfald 4.62V / 2.01%).

Hvor mange kW svarer 90A ved 230V til?

Det svarer til 20.7 kW med en anbefalet sikring på 90A.