⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 160 Ampere ved 30 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 160 A over 30 m ved 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 2.93V (1.28%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 3.57V (1.55%)
Voltage at Load227.1 VLine Loss: 469.6 W
Max Power & Breaker36.8 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A136.96 V (59.55%)93.0 V225.92 V (98.23%)21913.6 WDrop High
2.5 mm²24 A18 A82.18 V (35.73%)147.8 V135.55 V (58.94%)13148.2 WDrop High
4 mm²32 A25 A51.36 V (22.33%)178.6 V84.72 V (36.83%)8217.6 WDrop High
6 mm²41 A32 A34.24 V (14.89%)195.8 V56.48 V (24.56%)5478.4 WDrop High
10 mm²57 A44 A20.54 V (8.93%)209.5 V33.89 V (14.73%)3287.0 WDrop High
16 mm²76 A59 A12.84 V (5.58%)217.2 V21.18 V (9.21%)2054.4 WDrop High
25 mm²101 A78 A8.22 V (3.57%)221.8 V13.56 V (5.89%)1314.8 WDrop High
35 mm²125 A97 A5.87 V (2.55%)224.1 V9.68 V (4.21%)939.2 WDrop High
50 mm²151 A118 A4.11 V (1.79%)225.9 V6.78 V (2.95%)657.4 WDrop High
70 mm²192 A150 A2.93 V (1.28%)227.1 V4.84 V (2.1%)469.6 W✓ OK (≤3%)
95 mm²232 A181 A2.16 V (0.94%)227.8 V3.57 V (1.55%)346.0 W✓ OK (≤3%)
120 mm²269 A210 A1.71 V (0.74%)228.3 V2.82 V (1.23%)273.9 W✓ OK (≤3%)
150 mm²309 A241 A1.37 V (0.6%)228.6 V2.26 V (0.98%)219.1 W✓ OK (≤3%)
185 mm²353 A275 A1.11 V (0.48%)228.9 V1.83 V (0.8%)177.7 W✓ OK (≤3%)
240 mm²415 A324 A0.86 V (0.37%)229.1 V1.41 V (0.61%)137.0 W✓ OK (≤3%)
300 mm²477 A372 A0.68 V (0.3%)229.3 V1.13 V (0.49%)109.6 W✓ OK (≤3%)
400 mm²570 A445 A0.51 V (0.22%)229.5 V0.85 V (0.37%)82.2 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 160 Ampere ved 30 Meter (230V)

Hvilket kabeltværsnit kræves til 160A ved 30 meter (230V)?

Til 160 Ampere over 30 meter ved 230V anbefales 70 mm² kobberkabel (spændingsfald 2.93V / 1.28%).

Hvor mange kW svarer 160A ved 230V til?

Det svarer til 36.8 kW med en anbefalet sikring på 160A.