Kabeltværsnit for 90 Ampere ved 30 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 90 A over 30 m ved 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 4.0V (1.0%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 4.72V (1.18%)
Voltage at Load396.0 VLine Loss: 624.0 W
Max Power & Breaker62.35 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A66.72 V (16.68%)333.3 V110.05 V (27.51%)10400.4 WDrop High
2.5 mm²24 A18 A40.03 V (10.01%)360.0 V66.03 V (16.51%)6240.2 WDrop High
4 mm²32 A25 A25.02 V (6.25%)375.0 V41.27 V (10.32%)3900.2 WDrop High
6 mm²41 A32 A16.68 V (4.17%)383.3 V27.51 V (6.88%)2600.1 WDrop High
10 mm²57 A44 A10.01 V (2.5%)390.0 V16.51 V (4.13%)1560.1 WDrop High
16 mm²76 A59 A6.25 V (1.56%)393.7 V10.32 V (2.58%)975.0 WDrop High
25 mm²101 A78 A4.0 V (1.0%)396.0 V6.6 V (1.65%)624.0 W✓ OK (≤3%)
35 mm²125 A97 A2.86 V (0.71%)397.1 V4.72 V (1.18%)445.7 W✓ OK (≤3%)
50 mm²151 A118 A2.0 V (0.5%)398.0 V3.3 V (0.83%)312.0 W✓ OK (≤3%)
70 mm²192 A150 A1.43 V (0.36%)398.6 V2.36 V (0.59%)222.9 W✓ OK (≤3%)
95 mm²232 A181 A1.05 V (0.26%)398.9 V1.74 V (0.43%)164.2 W✓ OK (≤3%)
120 mm²269 A210 A0.83 V (0.21%)399.2 V1.38 V (0.34%)130.0 W✓ OK (≤3%)
150 mm²309 A241 A0.67 V (0.17%)399.3 V1.1 V (0.28%)104.0 W✓ OK (≤3%)
185 mm²353 A275 A0.54 V (0.14%)399.5 V0.89 V (0.22%)84.3 W✓ OK (≤3%)
240 mm²415 A324 A0.42 V (0.1%)399.6 V0.69 V (0.17%)65.0 W✓ OK (≤3%)
300 mm²477 A372 A0.33 V (0.08%)399.7 V0.55 V (0.14%)52.0 W✓ OK (≤3%)
400 mm²570 A445 A0.25 V (0.06%)399.7 V0.41 V (0.1%)39.0 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 90 Ampere ved 30 Meter (400V)

Hvilket kabeltværsnit kræves til 90A ved 30 meter (400V)?

Til 90 Ampere over 30 meter ved 400V anbefales 25 mm² kobberkabel (spændingsfald 4.0V / 1.0%).

Hvor mange kW svarer 90A ved 400V til?

Det svarer til 62.35 kW med en anbefalet sikring på 90A.