⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 900 Ampere ved 90 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 900 A over 90 m ved 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.75V (0.94%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.38V (3.1%)
Voltage at Load396.2 VLine Loss: 5850.2 W
Max Power & Breaker623.54 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2001.56 V (500.39%)0.0 V3301.64 V (825.41%)3120120.0 WDrop High
2.5 mm²24 A18 A1200.93 V (300.23%)0.0 V1980.98 V (495.25%)1872072.0 WDrop High
4 mm²32 A25 A750.58 V (187.65%)0.0 V1238.11 V (309.53%)1170045.0 WDrop High
6 mm²41 A32 A500.39 V (125.1%)0.0 V825.41 V (206.35%)780030.0 WDrop High
10 mm²57 A44 A300.23 V (75.06%)99.8 V495.25 V (123.81%)468018.0 WDrop High
16 mm²76 A59 A187.65 V (46.91%)212.4 V309.53 V (77.38%)292511.2 WDrop High
25 mm²101 A78 A120.09 V (30.02%)279.9 V198.1 V (49.52%)187207.2 WDrop High
35 mm²125 A97 A85.78 V (21.45%)314.2 V141.5 V (35.37%)133719.4 WDrop High
50 mm²151 A118 A60.05 V (15.01%)340.0 V99.05 V (24.76%)93603.6 WDrop High
70 mm²192 A150 A42.89 V (10.72%)357.1 V70.75 V (17.69%)66859.7 WDrop High
95 mm²232 A181 A31.6 V (7.9%)368.4 V52.13 V (13.03%)49265.1 WDrop High
120 mm²269 A210 A25.02 V (6.25%)375.0 V41.27 V (10.32%)39001.5 WDrop High
150 mm²309 A241 A20.02 V (5.0%)380.0 V33.02 V (8.25%)31201.2 WDrop High
185 mm²353 A275 A16.23 V (4.06%)383.8 V26.77 V (6.69%)25298.3 WDrop High
240 mm²415 A324 A12.51 V (3.13%)387.5 V20.64 V (5.16%)19500.7 WDrop High
300 mm²477 A372 A10.01 V (2.5%)390.0 V16.51 V (4.13%)15600.6 WDrop High
400 mm²570 A445 A7.51 V (1.88%)392.5 V12.38 V (3.1%)11700.4 WDrop High

FAQ — Kabeltværsnit for 900 Ampere ved 90 Meter (400V)

Hvilket kabeltværsnit kræves til 900A ved 90 meter (400V)?

Til 900 Ampere over 90 meter ved 400V anbefales 2× 400 mm² kobberkabel (spændingsfald 3.75V / 0.94%).

Hvor mange kW svarer 900A ved 400V til?

Det svarer til 623.54 kW med en anbefalet sikring på 1000A.