Kabeltværsnit for 16 Ampere ved 90 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 16 A over 90 m ved 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 8.9V (2.22%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 8.8V (2.2%)
Voltage at Load391.1 VLine Loss: 246.5 W
Max Power & Breaker11.09 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A35.58 V (8.9%)364.4 V58.7 V (14.67%)986.1 WDrop High
2.5 mm²24 A18 A21.35 V (5.34%)378.7 V35.22 V (8.8%)591.7 WDrop High
4 mm²32 A25 A13.34 V (3.34%)386.7 V22.01 V (5.5%)369.8 W~ ≤5%
6 mm²41 A32 A8.9 V (2.22%)391.1 V14.67 V (3.67%)246.5 W✓ OK (≤3%)
10 mm²57 A44 A5.34 V (1.33%)394.7 V8.8 V (2.2%)147.9 W✓ OK (≤3%)
16 mm²76 A59 A3.34 V (0.83%)396.7 V5.5 V (1.38%)92.4 W✓ OK (≤3%)
25 mm²101 A78 A2.13 V (0.53%)397.9 V3.52 V (0.88%)59.2 W✓ OK (≤3%)
35 mm²125 A97 A1.52 V (0.38%)398.5 V2.52 V (0.63%)42.3 W✓ OK (≤3%)
50 mm²151 A118 A1.07 V (0.27%)398.9 V1.76 V (0.44%)29.6 W✓ OK (≤3%)
70 mm²192 A150 A0.76 V (0.19%)399.2 V1.26 V (0.31%)21.1 W✓ OK (≤3%)
95 mm²232 A181 A0.56 V (0.14%)399.4 V0.93 V (0.23%)15.6 W✓ OK (≤3%)
120 mm²269 A210 A0.44 V (0.11%)399.6 V0.73 V (0.18%)12.3 W✓ OK (≤3%)
150 mm²309 A241 A0.36 V (0.09%)399.6 V0.59 V (0.15%)9.9 W✓ OK (≤3%)
185 mm²353 A275 A0.29 V (0.07%)399.7 V0.48 V (0.12%)8.0 W✓ OK (≤3%)
240 mm²415 A324 A0.22 V (0.06%)399.8 V0.37 V (0.09%)6.2 W✓ OK (≤3%)
300 mm²477 A372 A0.18 V (0.04%)399.8 V0.29 V (0.07%)4.9 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.03%)399.9 V0.22 V (0.06%)3.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 16 Ampere ved 90 Meter (400V)

Hvilket kabeltværsnit kræves til 16A ved 90 meter (400V)?

Til 16 Ampere over 90 meter ved 400V anbefales 6 mm² kobberkabel (spændingsfald 8.9V / 2.22%).

Hvor mange kW svarer 16A ved 400V til?

Det svarer til 11.09 kW med en anbefalet sikring på 16A.