Kabelquerschnitt für 10 Ampere bei 60 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 10 A über 60 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)4 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 4.24V (1.84%)
Voltage at Load223.6 VLine Loss: 64.2 W
Max Power & Breaker2.3 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A17.12 V (7.44%)212.9 V28.24 V (12.28%)171.2 WDrop High
2.5 mm²24 A18 A10.27 V (4.47%)219.7 V16.94 V (7.37%)102.7 W~ ≤5%
4 mm²32 A25 A6.42 V (2.79%)223.6 V10.59 V (4.6%)64.2 W✓ OK (≤3%)
6 mm²41 A32 A4.28 V (1.86%)225.7 V7.06 V (3.07%)42.8 W✓ OK (≤3%)
10 mm²57 A44 A2.57 V (1.12%)227.4 V4.24 V (1.84%)25.7 W✓ OK (≤3%)
16 mm²76 A59 A1.6 V (0.7%)228.4 V2.65 V (1.15%)16.1 W✓ OK (≤3%)
25 mm²101 A78 A1.03 V (0.45%)229.0 V1.69 V (0.74%)10.3 W✓ OK (≤3%)
35 mm²125 A97 A0.73 V (0.32%)229.3 V1.21 V (0.53%)7.3 W✓ OK (≤3%)
50 mm²151 A118 A0.51 V (0.22%)229.5 V0.85 V (0.37%)5.1 W✓ OK (≤3%)
70 mm²192 A150 A0.37 V (0.16%)229.6 V0.61 V (0.26%)3.7 W✓ OK (≤3%)
95 mm²232 A181 A0.27 V (0.12%)229.7 V0.45 V (0.19%)2.7 W✓ OK (≤3%)
120 mm²269 A210 A0.21 V (0.09%)229.8 V0.35 V (0.15%)2.1 W✓ OK (≤3%)
150 mm²309 A241 A0.17 V (0.07%)229.8 V0.28 V (0.12%)1.7 W✓ OK (≤3%)
185 mm²353 A275 A0.14 V (0.06%)229.9 V0.23 V (0.1%)1.4 W✓ OK (≤3%)
240 mm²415 A324 A0.11 V (0.05%)229.9 V0.18 V (0.08%)1.1 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.04%)229.9 V0.14 V (0.06%)0.9 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.03%)229.9 V0.11 V (0.05%)0.6 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 10 Ampere bei 60 Meter (230V)

Welcher Kabelquerschnitt wird für 10A bei 60m (230V) benötigt?

Für 10 Ampere über 60 Meter bei 230V wird ein Kupferkabel von 4 mm² empfohlen, um den Spannungsfall unter 3% (6.42V bzw. 2.79%) zu halten.

Wie hoch ist die maximale Leistung bei 10A und 230V?

Die übertragbare Leistung beträgt 2.3 kW bei einer empfohlenen Absicherung von 10A.