⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 10 Ampere bei 25 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 10 A über 25 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 4.28V (1.86%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 4.41V (1.92%)
Voltage at Load225.7 VLine Loss: 42.8 W
Max Power & Breaker2.3 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7.13 V (3.1%)222.9 V11.77 V (5.12%)71.3 W~ ≤5%
2.5 mm²24 A18 A4.28 V (1.86%)225.7 V7.06 V (3.07%)42.8 W✓ OK (≤3%)
4 mm²32 A25 A2.67 V (1.16%)227.3 V4.41 V (1.92%)26.7 W✓ OK (≤3%)
6 mm²41 A32 A1.78 V (0.78%)228.2 V2.94 V (1.28%)17.8 W✓ OK (≤3%)
10 mm²57 A44 A1.07 V (0.47%)228.9 V1.76 V (0.77%)10.7 W✓ OK (≤3%)
16 mm²76 A59 A0.67 V (0.29%)229.3 V1.1 V (0.48%)6.7 W✓ OK (≤3%)
25 mm²101 A78 A0.43 V (0.19%)229.6 V0.71 V (0.31%)4.3 W✓ OK (≤3%)
35 mm²125 A97 A0.31 V (0.13%)229.7 V0.5 V (0.22%)3.1 W✓ OK (≤3%)
50 mm²151 A118 A0.21 V (0.09%)229.8 V0.35 V (0.15%)2.1 W✓ OK (≤3%)
70 mm²192 A150 A0.15 V (0.07%)229.8 V0.25 V (0.11%)1.5 W✓ OK (≤3%)
95 mm²232 A181 A0.11 V (0.05%)229.9 V0.19 V (0.08%)1.1 W✓ OK (≤3%)
120 mm²269 A210 A0.09 V (0.04%)229.9 V0.15 V (0.06%)0.9 W✓ OK (≤3%)
150 mm²309 A241 A0.07 V (0.03%)229.9 V0.12 V (0.05%)0.7 W✓ OK (≤3%)
185 mm²353 A275 A0.06 V (0.03%)229.9 V0.1 V (0.04%)0.6 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.02%)230.0 V0.07 V (0.03%)0.4 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.02%)230.0 V0.06 V (0.03%)0.4 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.01%)230.0 V0.04 V (0.02%)0.3 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 10 Ampere bei 25 Meter (230V)

Welcher Kabelquerschnitt wird für 10A bei 25m (230V) benötigt?

Für 10 Ampere über 25 Meter bei 230V wird ein Kupferkabel von 2.5 mm² empfohlen, um den Spannungsfall unter 3% (4.28V bzw. 1.86%) zu halten.

Wie hoch ist die maximale Leistung bei 10A und 230V?

Die übertragbare Leistung beträgt 2.3 kW bei einer empfohlenen Absicherung von 10A.