⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 100 Ampere bei 10 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 100 A über 10 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 1.48V (0.37%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 1.22V (0.31%)
Voltage at Load398.5 VLine Loss: 256.8 W
Max Power & Breaker69.28 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A24.71 V (6.18%)375.3 V40.76 V (10.19%)4280.0 WDrop High
2.5 mm²24 A18 A14.83 V (3.71%)385.2 V24.46 V (6.11%)2568.0 WDrop High
4 mm²32 A25 A9.27 V (2.32%)390.7 V15.29 V (3.82%)1605.0 WDrop High
6 mm²41 A32 A6.18 V (1.54%)393.8 V10.19 V (2.55%)1070.0 WDrop High
10 mm²57 A44 A3.71 V (0.93%)396.3 V6.11 V (1.53%)642.0 WDrop High
16 mm²76 A59 A2.32 V (0.58%)397.7 V3.82 V (0.96%)401.2 WDrop High
25 mm²101 A78 A1.48 V (0.37%)398.5 V2.45 V (0.61%)256.8 W✓ OK (≤3%)
35 mm²125 A97 A1.06 V (0.26%)398.9 V1.75 V (0.44%)183.4 W✓ OK (≤3%)
50 mm²151 A118 A0.74 V (0.19%)399.3 V1.22 V (0.31%)128.4 W✓ OK (≤3%)
70 mm²192 A150 A0.53 V (0.13%)399.5 V0.87 V (0.22%)91.7 W✓ OK (≤3%)
95 mm²232 A181 A0.39 V (0.1%)399.6 V0.64 V (0.16%)67.6 W✓ OK (≤3%)
120 mm²269 A210 A0.31 V (0.08%)399.7 V0.51 V (0.13%)53.5 W✓ OK (≤3%)
150 mm²309 A241 A0.25 V (0.06%)399.8 V0.41 V (0.1%)42.8 W✓ OK (≤3%)
185 mm²353 A275 A0.2 V (0.05%)399.8 V0.33 V (0.08%)34.7 W✓ OK (≤3%)
240 mm²415 A324 A0.15 V (0.04%)399.8 V0.25 V (0.06%)26.8 W✓ OK (≤3%)
300 mm²477 A372 A0.12 V (0.03%)399.9 V0.2 V (0.05%)21.4 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.02%)399.9 V0.15 V (0.04%)16.1 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 100 Ampere bei 10 Meter (400V)

Welcher Kabelquerschnitt wird für 100A bei 10m (400V) benötigt?

Für 100 Ampere über 10 Meter bei 400V wird ein Kupferkabel von 25 mm² empfohlen, um den Spannungsfall unter 3% (1.48V bzw. 0.37%) zu halten.

Wie hoch ist die maximale Leistung bei 100A und 400V?

Die übertragbare Leistung beträgt 69.28 kW bei einer empfohlenen Absicherung von 100A.