⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 20 Ampere bei 10 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 20 A über 10 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 2.97V (0.74%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 3.06V (0.76%)
Voltage at Load397.0 VLine Loss: 102.7 W
Max Power & Breaker13.86 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4.94 V (1.24%)395.1 V8.15 V (2.04%)171.2 WDrop High
2.5 mm²24 A18 A2.97 V (0.74%)397.0 V4.89 V (1.22%)102.7 W✓ OK (≤3%)
4 mm²32 A25 A1.85 V (0.46%)398.1 V3.06 V (0.76%)64.2 W✓ OK (≤3%)
6 mm²41 A32 A1.24 V (0.31%)398.8 V2.04 V (0.51%)42.8 W✓ OK (≤3%)
10 mm²57 A44 A0.74 V (0.19%)399.3 V1.22 V (0.31%)25.7 W✓ OK (≤3%)
16 mm²76 A59 A0.46 V (0.12%)399.5 V0.76 V (0.19%)16.1 W✓ OK (≤3%)
25 mm²101 A78 A0.3 V (0.07%)399.7 V0.49 V (0.12%)10.3 W✓ OK (≤3%)
35 mm²125 A97 A0.21 V (0.05%)399.8 V0.35 V (0.09%)7.3 W✓ OK (≤3%)
50 mm²151 A118 A0.15 V (0.04%)399.9 V0.24 V (0.06%)5.1 W✓ OK (≤3%)
70 mm²192 A150 A0.11 V (0.03%)399.9 V0.17 V (0.04%)3.7 W✓ OK (≤3%)
95 mm²232 A181 A0.08 V (0.02%)399.9 V0.13 V (0.03%)2.7 W✓ OK (≤3%)
120 mm²269 A210 A0.06 V (0.02%)399.9 V0.1 V (0.03%)2.1 W✓ OK (≤3%)
150 mm²309 A241 A0.05 V (0.01%)400.0 V0.08 V (0.02%)1.7 W✓ OK (≤3%)
185 mm²353 A275 A0.04 V (0.01%)400.0 V0.07 V (0.02%)1.4 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.01%)400.0 V0.05 V (0.01%)1.1 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.01%)400.0 V0.04 V (0.01%)0.9 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.0%)400.0 V0.03 V (0.01%)0.6 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 20 Ampere bei 10 Meter (400V)

Welcher Kabelquerschnitt wird für 20A bei 10m (400V) benötigt?

Für 20 Ampere über 10 Meter bei 400V wird ein Kupferkabel von 2.5 mm² empfohlen, um den Spannungsfall unter 3% (2.97V bzw. 0.74%) zu halten.

Wie hoch ist die maximale Leistung bei 20A und 400V?

Die übertragbare Leistung beträgt 13.86 kW bei einer empfohlenen Absicherung von 20A.