⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 1000 Ampere bei 40 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 1000 A über 40 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.85V (0.47%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.11V (1.53%)
Voltage at Load398.1 VLine Loss: 3210.0 W
Max Power & Breaker692.82 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A988.42 V (247.11%)0.0 V1630.44 V (407.61%)1712000.0 WDrop High
2.5 mm²24 A18 A593.05 V (148.26%)0.0 V978.26 V (244.57%)1027200.0 WDrop High
4 mm²32 A25 A370.66 V (92.66%)29.3 V611.41 V (152.85%)642000.0 WDrop High
6 mm²41 A32 A247.11 V (61.78%)152.9 V407.61 V (101.9%)428000.0 WDrop High
10 mm²57 A44 A148.26 V (37.07%)251.7 V244.57 V (61.14%)256800.0 WDrop High
16 mm²76 A59 A92.66 V (23.17%)307.3 V152.85 V (38.21%)160500.0 WDrop High
25 mm²101 A78 A59.31 V (14.83%)340.7 V97.83 V (24.46%)102720.0 WDrop High
35 mm²125 A97 A42.36 V (10.59%)357.6 V69.88 V (17.47%)73371.4 WDrop High
50 mm²151 A118 A29.65 V (7.41%)370.3 V48.91 V (12.23%)51360.0 WDrop High
70 mm²192 A150 A21.18 V (5.3%)378.8 V34.94 V (8.73%)36685.7 WDrop High
95 mm²232 A181 A15.61 V (3.9%)384.4 V25.74 V (6.44%)27031.6 WDrop High
120 mm²269 A210 A12.36 V (3.09%)387.6 V20.38 V (5.1%)21400.0 WDrop High
150 mm²309 A241 A9.88 V (2.47%)390.1 V16.3 V (4.08%)17120.0 WDrop High
185 mm²353 A275 A8.01 V (2.0%)392.0 V13.22 V (3.3%)13881.1 WDrop High
240 mm²415 A324 A6.18 V (1.54%)393.8 V10.19 V (2.55%)10700.0 WDrop High
300 mm²477 A372 A4.94 V (1.24%)395.1 V8.15 V (2.04%)8560.0 WDrop High
400 mm²570 A445 A3.71 V (0.93%)396.3 V6.11 V (1.53%)6420.0 WDrop High

FAQ — Kabelquerschnitt für 1000 Ampere bei 40 Meter (400V)

Welcher Kabelquerschnitt wird für 1000A bei 40m (400V) benötigt?

Für 1000 Ampere über 40 Meter bei 400V wird ein Kupferkabel von 2× 400 mm² empfohlen, um den Spannungsfall unter 3% (1.85V bzw. 0.47%) zu halten.

Wie hoch ist die maximale Leistung bei 1000A und 400V?

Die übertragbare Leistung beträgt 692.82 kW bei einer empfohlenen Absicherung von 1000A.