⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 1000 Ampere bei 45 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 1000 A über 45 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.08V (0.52%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.88V (1.72%)
Voltage at Load397.9 VLine Loss: 3611.2 W
Max Power & Breaker692.82 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1111.98 V (277.99%)0.0 V1834.24 V (458.56%)1926000.0 WDrop High
2.5 mm²24 A18 A667.19 V (166.8%)0.0 V1100.55 V (275.14%)1155600.0 WDrop High
4 mm²32 A25 A416.99 V (104.25%)0.0 V687.84 V (171.96%)722250.0 WDrop High
6 mm²41 A32 A277.99 V (69.5%)122.0 V458.56 V (114.64%)481500.0 WDrop High
10 mm²57 A44 A166.8 V (41.7%)233.2 V275.14 V (68.78%)288900.0 WDrop High
16 mm²76 A59 A104.25 V (26.06%)295.8 V171.96 V (42.99%)180562.5 WDrop High
25 mm²101 A78 A66.72 V (16.68%)333.3 V110.05 V (27.51%)115560.0 WDrop High
35 mm²125 A97 A47.66 V (11.91%)352.3 V78.61 V (19.65%)82542.9 WDrop High
50 mm²151 A118 A33.36 V (8.34%)366.6 V55.03 V (13.76%)57780.0 WDrop High
70 mm²192 A150 A23.83 V (5.96%)376.2 V39.31 V (9.83%)41271.4 WDrop High
95 mm²232 A181 A17.56 V (4.39%)382.4 V28.96 V (7.24%)30410.5 WDrop High
120 mm²269 A210 A13.9 V (3.47%)386.1 V22.93 V (5.73%)24075.0 WDrop High
150 mm²309 A241 A11.12 V (2.78%)388.9 V18.34 V (4.59%)19260.0 WDrop High
185 mm²353 A275 A9.02 V (2.25%)391.0 V14.87 V (3.72%)15616.2 WDrop High
240 mm²415 A324 A6.95 V (1.74%)393.1 V11.46 V (2.87%)12037.5 WDrop High
300 mm²477 A372 A5.56 V (1.39%)394.4 V9.17 V (2.29%)9630.0 WDrop High
400 mm²570 A445 A4.17 V (1.04%)395.8 V6.88 V (1.72%)7222.5 WDrop High

FAQ — Kabelquerschnitt für 1000 Ampere bei 45 Meter (400V)

Welcher Kabelquerschnitt wird für 1000A bei 45m (400V) benötigt?

Für 1000 Ampere über 45 Meter bei 400V wird ein Kupferkabel von 2× 400 mm² empfohlen, um den Spannungsfall unter 3% (2.08V bzw. 0.52%) zu halten.

Wie hoch ist die maximale Leistung bei 1000A und 400V?

Die übertragbare Leistung beträgt 692.82 kW bei einer empfohlenen Absicherung von 1000A.