Kabelquerschnitt für 15 Ampere bei 150 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 15 A über 150 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 8.34V (2.08%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 8.6V (2.15%)
Voltage at Load391.7 VLine Loss: 216.7 W
Max Power & Breaker10.39 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A55.6 V (13.9%)344.4 V91.71 V (22.93%)1444.5 WDrop High
2.5 mm²24 A18 A33.36 V (8.34%)366.6 V55.03 V (13.76%)866.7 WDrop High
4 mm²32 A25 A20.85 V (5.21%)379.2 V34.39 V (8.6%)541.7 WDrop High
6 mm²41 A32 A13.9 V (3.47%)386.1 V22.93 V (5.73%)361.1 W~ ≤5%
10 mm²57 A44 A8.34 V (2.08%)391.7 V13.76 V (3.44%)216.7 W✓ OK (≤3%)
16 mm²76 A59 A5.21 V (1.3%)394.8 V8.6 V (2.15%)135.4 W✓ OK (≤3%)
25 mm²101 A78 A3.34 V (0.83%)396.7 V5.5 V (1.38%)86.7 W✓ OK (≤3%)
35 mm²125 A97 A2.38 V (0.6%)397.6 V3.93 V (0.98%)61.9 W✓ OK (≤3%)
50 mm²151 A118 A1.67 V (0.42%)398.3 V2.75 V (0.69%)43.3 W✓ OK (≤3%)
70 mm²192 A150 A1.19 V (0.3%)398.8 V1.97 V (0.49%)31.0 W✓ OK (≤3%)
95 mm²232 A181 A0.88 V (0.22%)399.1 V1.45 V (0.36%)22.8 W✓ OK (≤3%)
120 mm²269 A210 A0.69 V (0.17%)399.3 V1.15 V (0.29%)18.1 W✓ OK (≤3%)
150 mm²309 A241 A0.56 V (0.14%)399.4 V0.92 V (0.23%)14.4 W✓ OK (≤3%)
185 mm²353 A275 A0.45 V (0.11%)399.5 V0.74 V (0.19%)11.7 W✓ OK (≤3%)
240 mm²415 A324 A0.35 V (0.09%)399.7 V0.57 V (0.14%)9.0 W✓ OK (≤3%)
300 mm²477 A372 A0.28 V (0.07%)399.7 V0.46 V (0.11%)7.2 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.05%)399.8 V0.34 V (0.09%)5.4 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 15 Ampere bei 150 Meter (400V)

Welcher Kabelquerschnitt wird für 15A bei 150m (400V) benötigt?

Für 15 Ampere über 150 Meter bei 400V wird ein Kupferkabel von 10 mm² empfohlen, um den Spannungsfall unter 3% (8.34V bzw. 2.08%) zu halten.

Wie hoch ist die maximale Leistung bei 15A und 400V?

Die übertragbare Leistung beträgt 10.39 kW bei einer empfohlenen Absicherung von 15A.