Kabelquerschnitt für 15 Ampere bei 30 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 15 A über 30 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 11.01V (2.75%)
Voltage at Load388.9 VLine Loss: 288.9 W
Max Power & Breaker10.39 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11.12 V (2.78%)388.9 V18.34 V (4.59%)288.9 W✓ OK (≤3%)
2.5 mm²24 A18 A6.67 V (1.67%)393.3 V11.01 V (2.75%)173.3 W✓ OK (≤3%)
4 mm²32 A25 A4.17 V (1.04%)395.8 V6.88 V (1.72%)108.3 W✓ OK (≤3%)
6 mm²41 A32 A2.78 V (0.69%)397.2 V4.59 V (1.15%)72.2 W✓ OK (≤3%)
10 mm²57 A44 A1.67 V (0.42%)398.3 V2.75 V (0.69%)43.3 W✓ OK (≤3%)
16 mm²76 A59 A1.04 V (0.26%)399.0 V1.72 V (0.43%)27.1 W✓ OK (≤3%)
25 mm²101 A78 A0.67 V (0.17%)399.3 V1.1 V (0.28%)17.3 W✓ OK (≤3%)
35 mm²125 A97 A0.48 V (0.12%)399.5 V0.79 V (0.2%)12.4 W✓ OK (≤3%)
50 mm²151 A118 A0.33 V (0.08%)399.7 V0.55 V (0.14%)8.7 W✓ OK (≤3%)
70 mm²192 A150 A0.24 V (0.06%)399.8 V0.39 V (0.1%)6.2 W✓ OK (≤3%)
95 mm²232 A181 A0.18 V (0.04%)399.8 V0.29 V (0.07%)4.6 W✓ OK (≤3%)
120 mm²269 A210 A0.14 V (0.03%)399.9 V0.23 V (0.06%)3.6 W✓ OK (≤3%)
150 mm²309 A241 A0.11 V (0.03%)399.9 V0.18 V (0.05%)2.9 W✓ OK (≤3%)
185 mm²353 A275 A0.09 V (0.02%)399.9 V0.15 V (0.04%)2.3 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.02%)399.9 V0.11 V (0.03%)1.8 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.01%)399.9 V0.09 V (0.02%)1.4 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.01%)400.0 V0.07 V (0.02%)1.1 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 15 Ampere bei 30 Meter (400V)

Welcher Kabelquerschnitt wird für 15A bei 30m (400V) benötigt?

Für 15 Ampere über 30 Meter bei 400V wird ein Kupferkabel von 1.5 mm² empfohlen, um den Spannungsfall unter 3% (11.12V bzw. 2.78%) zu halten.

Wie hoch ist die maximale Leistung bei 15A und 400V?

Die übertragbare Leistung beträgt 10.39 kW bei einer empfohlenen Absicherung von 15A.