Kabelquerschnitt für 150 Ampere bei 5 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 150 A über 5 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)50 mm²Drop: 0.64V (0.28%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 0.76V (0.33%)
Voltage at Load229.4 VLine Loss: 96.3 W
Max Power & Breaker34.5 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A21.4 V (9.3%)208.6 V35.3 V (15.35%)3210.0 WDrop High
2.5 mm²24 A18 A12.84 V (5.58%)217.2 V21.18 V (9.21%)1926.0 WDrop High
4 mm²32 A25 A8.03 V (3.49%)222.0 V13.24 V (5.76%)1203.8 WDrop High
6 mm²41 A32 A5.35 V (2.33%)224.7 V8.82 V (3.84%)802.5 WDrop High
10 mm²57 A44 A3.21 V (1.4%)226.8 V5.29 V (2.3%)481.5 WDrop High
16 mm²76 A59 A2.01 V (0.87%)228.0 V3.31 V (1.44%)300.9 WDrop High
25 mm²101 A78 A1.28 V (0.56%)228.7 V2.12 V (0.92%)192.6 WDrop High
35 mm²125 A97 A0.92 V (0.4%)229.1 V1.51 V (0.66%)137.6 WDrop High
50 mm²151 A118 A0.64 V (0.28%)229.4 V1.06 V (0.46%)96.3 W✓ OK (≤3%)
70 mm²192 A150 A0.46 V (0.2%)229.5 V0.76 V (0.33%)68.8 W✓ OK (≤3%)
95 mm²232 A181 A0.34 V (0.15%)229.7 V0.56 V (0.24%)50.7 W✓ OK (≤3%)
120 mm²269 A210 A0.27 V (0.12%)229.7 V0.44 V (0.19%)40.1 W✓ OK (≤3%)
150 mm²309 A241 A0.21 V (0.09%)229.8 V0.35 V (0.15%)32.1 W✓ OK (≤3%)
185 mm²353 A275 A0.17 V (0.08%)229.8 V0.29 V (0.12%)26.0 W✓ OK (≤3%)
240 mm²415 A324 A0.13 V (0.06%)229.9 V0.22 V (0.1%)20.1 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.05%)229.9 V0.18 V (0.08%)16.1 W✓ OK (≤3%)
400 mm²570 A445 A0.08 V (0.03%)229.9 V0.13 V (0.06%)12.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 150 Ampere bei 5 Meter (230V)

Welcher Kabelquerschnitt wird für 150A bei 5m (230V) benötigt?

Für 150 Ampere über 5 Meter bei 230V wird ein Kupferkabel von 50 mm² empfohlen, um den Spannungsfall unter 3% (0.64V bzw. 0.28%) zu halten.

Wie hoch ist die maximale Leistung bei 150A und 230V?

Die übertragbare Leistung beträgt 34.5 kW bei einer empfohlenen Absicherung von 150A.