⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 150 Ampere bei 600 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 150 A über 600 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 13.76V (3.44%)
Voltage at Load388.9 VLine Loss: 2889.0 W
Max Power & Breaker103.92 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2223.95 V (555.99%)0.0 V3668.48 V (917.12%)577800.0 WDrop High
2.5 mm²24 A18 A1334.37 V (333.59%)0.0 V2201.09 V (550.27%)346680.0 WDrop High
4 mm²32 A25 A833.98 V (208.5%)0.0 V1375.68 V (343.92%)216675.0 WDrop High
6 mm²41 A32 A555.99 V (139.0%)0.0 V917.12 V (229.28%)144450.0 WDrop High
10 mm²57 A44 A333.59 V (83.4%)66.4 V550.27 V (137.57%)86670.0 WDrop High
16 mm²76 A59 A208.5 V (52.12%)191.5 V343.92 V (85.98%)54168.8 WDrop High
25 mm²101 A78 A133.44 V (33.36%)266.6 V220.11 V (55.03%)34668.0 WDrop High
35 mm²125 A97 A95.31 V (23.83%)304.7 V157.22 V (39.31%)24762.9 WDrop High
50 mm²151 A118 A66.72 V (16.68%)333.3 V110.05 V (27.51%)17334.0 WDrop High
70 mm²192 A150 A47.66 V (11.91%)352.3 V78.61 V (19.65%)12381.4 WDrop High
95 mm²232 A181 A35.12 V (8.78%)364.9 V57.92 V (14.48%)9123.2 WDrop High
120 mm²269 A210 A27.8 V (6.95%)372.2 V45.86 V (11.46%)7222.5 WDrop High
150 mm²309 A241 A22.24 V (5.56%)377.8 V36.68 V (9.17%)5778.0 WDrop High
185 mm²353 A275 A18.03 V (4.51%)382.0 V29.74 V (7.44%)4684.9 W~ ≤5%
240 mm²415 A324 A13.9 V (3.47%)386.1 V22.93 V (5.73%)3611.2 W~ ≤5%
300 mm²477 A372 A11.12 V (2.78%)388.9 V18.34 V (4.59%)2889.0 W✓ OK (≤3%)
400 mm²570 A445 A8.34 V (2.08%)391.7 V13.76 V (3.44%)2166.7 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 150 Ampere bei 600 Meter (400V)

Welcher Kabelquerschnitt wird für 150A bei 600m (400V) benötigt?

Für 150 Ampere über 600 Meter bei 400V wird ein Kupferkabel von 300 mm² empfohlen, um den Spannungsfall unter 3% (11.12V bzw. 2.78%) zu halten.

Wie hoch ist die maximale Leistung bei 150A und 400V?

Die übertragbare Leistung beträgt 103.92 kW bei einer empfohlenen Absicherung von 150A.