Kabelquerschnitt für 125 Ampere bei 600 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 125 A über 600 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 11.58V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.46V (2.87%)
Voltage at Load388.4 VLine Loss: 2507.8 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1853.29 V (463.32%)0.0 V3057.07 V (764.27%)401250.0 WDrop High
2.5 mm²24 A18 A1111.98 V (277.99%)0.0 V1834.24 V (458.56%)240750.0 WDrop High
4 mm²32 A25 A694.99 V (173.75%)0.0 V1146.4 V (286.6%)150468.8 WDrop High
6 mm²41 A32 A463.32 V (115.83%)0.0 V764.27 V (191.07%)100312.5 WDrop High
10 mm²57 A44 A277.99 V (69.5%)122.0 V458.56 V (114.64%)60187.5 WDrop High
16 mm²76 A59 A173.75 V (43.44%)226.3 V286.6 V (71.65%)37617.2 WDrop High
25 mm²101 A78 A111.2 V (27.8%)288.8 V183.42 V (45.86%)24075.0 WDrop High
35 mm²125 A97 A79.43 V (19.86%)320.6 V131.02 V (32.75%)17196.4 WDrop High
50 mm²151 A118 A55.6 V (13.9%)344.4 V91.71 V (22.93%)12037.5 WDrop High
70 mm²192 A150 A39.71 V (9.93%)360.3 V65.51 V (16.38%)8598.2 WDrop High
95 mm²232 A181 A29.26 V (7.32%)370.7 V48.27 V (12.07%)6335.5 WDrop High
120 mm²269 A210 A23.17 V (5.79%)376.8 V38.21 V (9.55%)5015.6 WDrop High
150 mm²309 A241 A18.53 V (4.63%)381.5 V30.57 V (7.64%)4012.5 W~ ≤5%
185 mm²353 A275 A15.03 V (3.76%)385.0 V24.79 V (6.2%)3253.4 W~ ≤5%
240 mm²415 A324 A11.58 V (2.9%)388.4 V19.11 V (4.78%)2507.8 W✓ OK (≤3%)
300 mm²477 A372 A9.27 V (2.32%)390.7 V15.29 V (3.82%)2006.2 W✓ OK (≤3%)
400 mm²570 A445 A6.95 V (1.74%)393.1 V11.46 V (2.87%)1504.7 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 125 Ampere bei 600 Meter (400V)

Welcher Kabelquerschnitt wird für 125A bei 600m (400V) benötigt?

Für 125 Ampere über 600 Meter bei 400V wird ein Kupferkabel von 240 mm² empfohlen, um den Spannungsfall unter 3% (11.58V bzw. 2.9%) zu halten.

Wie hoch ist die maximale Leistung bei 125A und 400V?

Die übertragbare Leistung beträgt 86.6 kW bei einer empfohlenen Absicherung von 125A.