Kabelquerschnitt für 160 Ampere bei 200 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 160 A über 200 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 9.88V (2.47%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 10.58V (2.64%)
Voltage at Load390.1 VLine Loss: 2739.2 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A790.74 V (197.68%)0.0 V1304.35 V (326.09%)219136.0 WDrop High
2.5 mm²24 A18 A474.44 V (118.61%)0.0 V782.61 V (195.65%)131481.6 WDrop High
4 mm²32 A25 A296.53 V (74.13%)103.5 V489.13 V (122.28%)82176.0 WDrop High
6 mm²41 A32 A197.68 V (49.42%)202.3 V326.09 V (81.52%)54784.0 WDrop High
10 mm²57 A44 A118.61 V (29.65%)281.4 V195.65 V (48.91%)32870.4 WDrop High
16 mm²76 A59 A74.13 V (18.53%)325.9 V122.28 V (30.57%)20544.0 WDrop High
25 mm²101 A78 A47.44 V (11.86%)352.6 V78.26 V (19.57%)13148.2 WDrop High
35 mm²125 A97 A33.89 V (8.47%)366.1 V55.9 V (13.98%)9391.5 WDrop High
50 mm²151 A118 A23.72 V (5.93%)376.3 V39.13 V (9.78%)6574.1 WDrop High
70 mm²192 A150 A16.94 V (4.24%)383.1 V27.95 V (6.99%)4695.8 W~ ≤5%
95 mm²232 A181 A12.49 V (3.12%)387.5 V20.59 V (5.15%)3460.0 W~ ≤5%
120 mm²269 A210 A9.88 V (2.47%)390.1 V16.3 V (4.08%)2739.2 W✓ OK (≤3%)
150 mm²309 A241 A7.91 V (1.98%)392.1 V13.04 V (3.26%)2191.4 W✓ OK (≤3%)
185 mm²353 A275 A6.41 V (1.6%)393.6 V10.58 V (2.64%)1776.8 W✓ OK (≤3%)
240 mm²415 A324 A4.94 V (1.24%)395.1 V8.15 V (2.04%)1369.6 W✓ OK (≤3%)
300 mm²477 A372 A3.95 V (0.99%)396.0 V6.52 V (1.63%)1095.7 W✓ OK (≤3%)
400 mm²570 A445 A2.97 V (0.74%)397.0 V4.89 V (1.22%)821.8 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 160 Ampere bei 200 Meter (400V)

Welcher Kabelquerschnitt wird für 160A bei 200m (400V) benötigt?

Für 160 Ampere über 200 Meter bei 400V wird ein Kupferkabel von 120 mm² empfohlen, um den Spannungsfall unter 3% (9.88V bzw. 2.47%) zu halten.

Wie hoch ist die maximale Leistung bei 160A und 400V?

Die übertragbare Leistung beträgt 110.85 kW bei einer empfohlenen Absicherung von 160A.