Kabelquerschnitt für 20 Ampere bei 250 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 20 A über 250 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 11.58V (2.9%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 8.73V (2.18%)
Voltage at Load388.4 VLine Loss: 401.2 W
Max Power & Breaker13.86 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A123.55 V (30.89%)276.4 V203.8 V (50.95%)4280.0 WDrop High
2.5 mm²24 A18 A74.13 V (18.53%)325.9 V122.28 V (30.57%)2568.0 WDrop High
4 mm²32 A25 A46.33 V (11.58%)353.7 V76.43 V (19.11%)1605.0 WDrop High
6 mm²41 A32 A30.89 V (7.72%)369.1 V50.95 V (12.74%)1070.0 WDrop High
10 mm²57 A44 A18.53 V (4.63%)381.5 V30.57 V (7.64%)642.0 W~ ≤5%
16 mm²76 A59 A11.58 V (2.9%)388.4 V19.11 V (4.78%)401.2 W✓ OK (≤3%)
25 mm²101 A78 A7.41 V (1.85%)392.6 V12.23 V (3.06%)256.8 W✓ OK (≤3%)
35 mm²125 A97 A5.3 V (1.32%)394.7 V8.73 V (2.18%)183.4 W✓ OK (≤3%)
50 mm²151 A118 A3.71 V (0.93%)396.3 V6.11 V (1.53%)128.4 W✓ OK (≤3%)
70 mm²192 A150 A2.65 V (0.66%)397.4 V4.37 V (1.09%)91.7 W✓ OK (≤3%)
95 mm²232 A181 A1.95 V (0.49%)398.0 V3.22 V (0.8%)67.6 W✓ OK (≤3%)
120 mm²269 A210 A1.54 V (0.39%)398.5 V2.55 V (0.64%)53.5 W✓ OK (≤3%)
150 mm²309 A241 A1.24 V (0.31%)398.8 V2.04 V (0.51%)42.8 W✓ OK (≤3%)
185 mm²353 A275 A1.0 V (0.25%)399.0 V1.65 V (0.41%)34.7 W✓ OK (≤3%)
240 mm²415 A324 A0.77 V (0.19%)399.2 V1.27 V (0.32%)26.7 W✓ OK (≤3%)
300 mm²477 A372 A0.62 V (0.15%)399.4 V1.02 V (0.25%)21.4 W✓ OK (≤3%)
400 mm²570 A445 A0.46 V (0.12%)399.5 V0.76 V (0.19%)16.1 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 20 Ampere bei 250 Meter (400V)

Welcher Kabelquerschnitt wird für 20A bei 250m (400V) benötigt?

Für 20 Ampere über 250 Meter bei 400V wird ein Kupferkabel von 16 mm² empfohlen, um den Spannungsfall unter 3% (11.58V bzw. 2.9%) zu halten.

Wie hoch ist die maximale Leistung bei 20A und 400V?

Die übertragbare Leistung beträgt 13.86 kW bei einer empfohlenen Absicherung von 20A.