⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 200 Ampere bei 60 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 200 A über 60 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 4.68V (1.17%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 6.11V (1.53%)
Voltage at Load395.3 VLine Loss: 1621.9 W
Max Power & Breaker138.56 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A296.53 V (74.13%)103.5 V489.13 V (122.28%)102720.0 WDrop High
2.5 mm²24 A18 A177.92 V (44.48%)222.1 V293.48 V (73.37%)61632.0 WDrop High
4 mm²32 A25 A111.2 V (27.8%)288.8 V183.42 V (45.86%)38520.0 WDrop High
6 mm²41 A32 A74.13 V (18.53%)325.9 V122.28 V (30.57%)25680.0 WDrop High
10 mm²57 A44 A44.48 V (11.12%)355.5 V73.37 V (18.34%)15408.0 WDrop High
16 mm²76 A59 A27.8 V (6.95%)372.2 V45.86 V (11.46%)9630.0 WDrop High
25 mm²101 A78 A17.79 V (4.45%)382.2 V29.35 V (7.34%)6163.2 WDrop High
35 mm²125 A97 A12.71 V (3.18%)387.3 V20.96 V (5.24%)4402.3 WDrop High
50 mm²151 A118 A8.9 V (2.22%)391.1 V14.67 V (3.67%)3081.6 WDrop High
70 mm²192 A150 A6.35 V (1.59%)393.6 V10.48 V (2.62%)2201.1 WDrop High
95 mm²232 A181 A4.68 V (1.17%)395.3 V7.72 V (1.93%)1621.9 W✓ OK (≤3%)
120 mm²269 A210 A3.71 V (0.93%)396.3 V6.11 V (1.53%)1284.0 W✓ OK (≤3%)
150 mm²309 A241 A2.97 V (0.74%)397.0 V4.89 V (1.22%)1027.2 W✓ OK (≤3%)
185 mm²353 A275 A2.4 V (0.6%)397.6 V3.97 V (0.99%)832.9 W✓ OK (≤3%)
240 mm²415 A324 A1.85 V (0.46%)398.1 V3.06 V (0.76%)642.0 W✓ OK (≤3%)
300 mm²477 A372 A1.48 V (0.37%)398.5 V2.45 V (0.61%)513.6 W✓ OK (≤3%)
400 mm²570 A445 A1.11 V (0.28%)398.9 V1.83 V (0.46%)385.2 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 200 Ampere bei 60 Meter (400V)

Welcher Kabelquerschnitt wird für 200A bei 60m (400V) benötigt?

Für 200 Ampere über 60 Meter bei 400V wird ein Kupferkabel von 95 mm² empfohlen, um den Spannungsfall unter 3% (4.68V bzw. 1.17%) zu halten.

Wie hoch ist die maximale Leistung bei 200A und 400V?

Die übertragbare Leistung beträgt 138.56 kW bei einer empfohlenen Absicherung von 200A.