⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 25 Ampere bei 60 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 25 A über 60 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 9.17V (2.29%)
Voltage at Load390.7 VLine Loss: 401.2 W
Max Power & Breaker17.32 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A37.07 V (9.27%)362.9 V61.14 V (15.29%)1605.0 WDrop High
2.5 mm²24 A18 A22.24 V (5.56%)377.8 V36.68 V (9.17%)963.0 WDrop High
4 mm²32 A25 A13.9 V (3.47%)386.1 V22.93 V (5.73%)601.9 W~ ≤5%
6 mm²41 A32 A9.27 V (2.32%)390.7 V15.29 V (3.82%)401.2 W✓ OK (≤3%)
10 mm²57 A44 A5.56 V (1.39%)394.4 V9.17 V (2.29%)240.8 W✓ OK (≤3%)
16 mm²76 A59 A3.47 V (0.87%)396.5 V5.73 V (1.43%)150.5 W✓ OK (≤3%)
25 mm²101 A78 A2.22 V (0.56%)397.8 V3.67 V (0.92%)96.3 W✓ OK (≤3%)
35 mm²125 A97 A1.59 V (0.4%)398.4 V2.62 V (0.66%)68.8 W✓ OK (≤3%)
50 mm²151 A118 A1.11 V (0.28%)398.9 V1.83 V (0.46%)48.2 W✓ OK (≤3%)
70 mm²192 A150 A0.79 V (0.2%)399.2 V1.31 V (0.33%)34.4 W✓ OK (≤3%)
95 mm²232 A181 A0.59 V (0.15%)399.4 V0.97 V (0.24%)25.3 W✓ OK (≤3%)
120 mm²269 A210 A0.46 V (0.12%)399.5 V0.76 V (0.19%)20.1 W✓ OK (≤3%)
150 mm²309 A241 A0.37 V (0.09%)399.6 V0.61 V (0.15%)16.1 W✓ OK (≤3%)
185 mm²353 A275 A0.3 V (0.08%)399.7 V0.5 V (0.12%)13.0 W✓ OK (≤3%)
240 mm²415 A324 A0.23 V (0.06%)399.8 V0.38 V (0.1%)10.0 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.05%)399.8 V0.31 V (0.08%)8.0 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.03%)399.9 V0.23 V (0.06%)6.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 25 Ampere bei 60 Meter (400V)

Welcher Kabelquerschnitt wird für 25A bei 60m (400V) benötigt?

Für 25 Ampere über 60 Meter bei 400V wird ein Kupferkabel von 6 mm² empfohlen, um den Spannungsfall unter 3% (9.27V bzw. 2.32%) zu halten.

Wie hoch ist die maximale Leistung bei 25A und 400V?

Die übertragbare Leistung beträgt 17.32 kW bei einer empfohlenen Absicherung von 25A.