Kabelquerschnitt für 25 Ampere bei 40 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 25 A über 40 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 4.28V (1.86%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 4.41V (1.92%)
Voltage at Load225.7 VLine Loss: 107.0 W
Max Power & Breaker5.75 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A28.53 V (12.41%)201.5 V47.07 V (20.46%)713.3 WDrop High
2.5 mm²24 A18 A17.12 V (7.44%)212.9 V28.24 V (12.28%)428.0 WDrop High
4 mm²32 A25 A10.7 V (4.65%)219.3 V17.65 V (7.67%)267.5 W~ ≤5%
6 mm²41 A32 A7.13 V (3.1%)222.9 V11.77 V (5.12%)178.3 W~ ≤5%
10 mm²57 A44 A4.28 V (1.86%)225.7 V7.06 V (3.07%)107.0 W✓ OK (≤3%)
16 mm²76 A59 A2.67 V (1.16%)227.3 V4.41 V (1.92%)66.9 W✓ OK (≤3%)
25 mm²101 A78 A1.71 V (0.74%)228.3 V2.82 V (1.23%)42.8 W✓ OK (≤3%)
35 mm²125 A97 A1.22 V (0.53%)228.8 V2.02 V (0.88%)30.6 W✓ OK (≤3%)
50 mm²151 A118 A0.86 V (0.37%)229.1 V1.41 V (0.61%)21.4 W✓ OK (≤3%)
70 mm²192 A150 A0.61 V (0.27%)229.4 V1.01 V (0.44%)15.3 W✓ OK (≤3%)
95 mm²232 A181 A0.45 V (0.2%)229.5 V0.74 V (0.32%)11.3 W✓ OK (≤3%)
120 mm²269 A210 A0.36 V (0.16%)229.6 V0.59 V (0.26%)8.9 W✓ OK (≤3%)
150 mm²309 A241 A0.29 V (0.12%)229.7 V0.47 V (0.2%)7.1 W✓ OK (≤3%)
185 mm²353 A275 A0.23 V (0.1%)229.8 V0.38 V (0.17%)5.8 W✓ OK (≤3%)
240 mm²415 A324 A0.18 V (0.08%)229.8 V0.29 V (0.13%)4.5 W✓ OK (≤3%)
300 mm²477 A372 A0.14 V (0.06%)229.9 V0.24 V (0.1%)3.6 W✓ OK (≤3%)
400 mm²570 A445 A0.11 V (0.05%)229.9 V0.18 V (0.08%)2.7 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 25 Ampere bei 40 Meter (230V)

Welcher Kabelquerschnitt wird für 25A bei 40m (230V) benötigt?

Für 25 Ampere über 40 Meter bei 230V wird ein Kupferkabel von 10 mm² empfohlen, um den Spannungsfall unter 3% (4.28V bzw. 1.86%) zu halten.

Wie hoch ist die maximale Leistung bei 25A und 230V?

Die übertragbare Leistung beträgt 5.75 kW bei einer empfohlenen Absicherung von 25A.