Kabelquerschnitt für 25 Ampere bei 25 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 25 A über 25 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)4 mm²Drop: 6.69V (2.91%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 4.41V (1.92%)
Voltage at Load223.3 VLine Loss: 167.2 W
Max Power & Breaker5.75 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A17.83 V (7.75%)212.2 V29.42 V (12.79%)445.8 WDrop High
2.5 mm²24 A18 A10.7 V (4.65%)219.3 V17.65 V (7.67%)267.5 WDrop High
4 mm²32 A25 A6.69 V (2.91%)223.3 V11.03 V (4.8%)167.2 W✓ OK (≤3%)
6 mm²41 A32 A4.46 V (1.94%)225.5 V7.35 V (3.2%)111.5 W✓ OK (≤3%)
10 mm²57 A44 A2.67 V (1.16%)227.3 V4.41 V (1.92%)66.9 W✓ OK (≤3%)
16 mm²76 A59 A1.67 V (0.73%)228.3 V2.76 V (1.2%)41.8 W✓ OK (≤3%)
25 mm²101 A78 A1.07 V (0.47%)228.9 V1.76 V (0.77%)26.7 W✓ OK (≤3%)
35 mm²125 A97 A0.76 V (0.33%)229.2 V1.26 V (0.55%)19.1 W✓ OK (≤3%)
50 mm²151 A118 A0.53 V (0.23%)229.5 V0.88 V (0.38%)13.4 W✓ OK (≤3%)
70 mm²192 A150 A0.38 V (0.17%)229.6 V0.63 V (0.27%)9.6 W✓ OK (≤3%)
95 mm²232 A181 A0.28 V (0.12%)229.7 V0.46 V (0.2%)7.0 W✓ OK (≤3%)
120 mm²269 A210 A0.22 V (0.1%)229.8 V0.37 V (0.16%)5.6 W✓ OK (≤3%)
150 mm²309 A241 A0.18 V (0.08%)229.8 V0.29 V (0.13%)4.5 W✓ OK (≤3%)
185 mm²353 A275 A0.14 V (0.06%)229.9 V0.24 V (0.1%)3.6 W✓ OK (≤3%)
240 mm²415 A324 A0.11 V (0.05%)229.9 V0.18 V (0.08%)2.8 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.04%)229.9 V0.15 V (0.06%)2.2 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.03%)229.9 V0.11 V (0.05%)1.7 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 25 Ampere bei 25 Meter (230V)

Welcher Kabelquerschnitt wird für 25A bei 25m (230V) benötigt?

Für 25 Ampere über 25 Meter bei 230V wird ein Kupferkabel von 4 mm² empfohlen, um den Spannungsfall unter 3% (6.69V bzw. 2.91%) zu halten.

Wie hoch ist die maximale Leistung bei 25A und 230V?

Die übertragbare Leistung beträgt 5.75 kW bei einer empfohlenen Absicherung von 25A.