Kabelquerschnitt für 250 Ampere bei 150 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 250 A über 150 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 11.58V (2.9%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 9.55V (2.39%)
Voltage at Load388.4 VLine Loss: 5015.6 W
Max Power & Breaker173.21 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A926.65 V (231.66%)0.0 V1528.53 V (382.13%)401250.0 WDrop High
2.5 mm²24 A18 A555.99 V (139.0%)0.0 V917.12 V (229.28%)240750.0 WDrop High
4 mm²32 A25 A347.49 V (86.87%)52.5 V573.2 V (143.3%)150468.8 WDrop High
6 mm²41 A32 A231.66 V (57.92%)168.3 V382.13 V (95.53%)100312.5 WDrop High
10 mm²57 A44 A139.0 V (34.75%)261.0 V229.28 V (57.32%)60187.5 WDrop High
16 mm²76 A59 A86.87 V (21.72%)313.1 V143.3 V (35.83%)37617.2 WDrop High
25 mm²101 A78 A55.6 V (13.9%)344.4 V91.71 V (22.93%)24075.0 WDrop High
35 mm²125 A97 A39.71 V (9.93%)360.3 V65.51 V (16.38%)17196.4 WDrop High
50 mm²151 A118 A27.8 V (6.95%)372.2 V45.86 V (11.46%)12037.5 WDrop High
70 mm²192 A150 A19.86 V (4.96%)380.1 V32.75 V (8.19%)8598.2 WDrop High
95 mm²232 A181 A14.63 V (3.66%)385.4 V24.13 V (6.03%)6335.5 WDrop High
120 mm²269 A210 A11.58 V (2.9%)388.4 V19.11 V (4.78%)5015.6 W✓ OK (≤3%)
150 mm²309 A241 A9.27 V (2.32%)390.7 V15.29 V (3.82%)4012.5 W✓ OK (≤3%)
185 mm²353 A275 A7.51 V (1.88%)392.5 V12.39 V (3.1%)3253.4 W✓ OK (≤3%)
240 mm²415 A324 A5.79 V (1.45%)394.2 V9.55 V (2.39%)2507.8 W✓ OK (≤3%)
300 mm²477 A372 A4.63 V (1.16%)395.4 V7.64 V (1.91%)2006.2 W✓ OK (≤3%)
400 mm²570 A445 A3.47 V (0.87%)396.5 V5.73 V (1.43%)1504.7 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 250 Ampere bei 150 Meter (400V)

Welcher Kabelquerschnitt wird für 250A bei 150m (400V) benötigt?

Für 250 Ampere über 150 Meter bei 400V wird ein Kupferkabel von 120 mm² empfohlen, um den Spannungsfall unter 3% (11.58V bzw. 2.9%) zu halten.

Wie hoch ist die maximale Leistung bei 250A und 400V?

Die übertragbare Leistung beträgt 173.21 kW bei einer empfohlenen Absicherung von 250A.